Setting via software parameters (AUMA CDT)
Condition: Switch [S5] is in position ON (software mode).
Setting parameters
Customer settings
Type of seating
End position CLOSED
End position OPEN
Default value:
Limit
Setting values:
Limit
Limit seating in end positions.
Torque
Torque seating in end positions.
9.4.
Torque switching: set
Valve damage due to excessive tripping torque limit setting!
→
The tripping torque must suit the valve.
→
Only change the setting with the consent of the valve manufacturer.
Once the set tripping torque is reached, the controls automatically switch off the
actuator (overload protection of the valve).
Setting via switches
Condition: Switch [S5] is in position OFF (hardware mode).
Figure 19: Switches for tripping torque
[S6]
Tripping torque in direction OPEN
[S7]
Tripping torque in direction CLOSE
Default value: depending on the order
Setting range: in 8 steps (refer to tables), linear from 40 – 100 % of the maximum
tripping torque.
Table 10:
Tripping torques [Nm]
Switch steps
SVM/SVMR 07.5
SVM/SVMR 07.1
SVM/SVMR 05.1
40
20
10
0 - 1
>
>
>
2 - 3
60
30
15
4
>
>
>
5
80
40
20
6
27
SVM 05.1 – SVM 07.5 / SVMR 05.1 – SVMR 07.5
Modbus RTU
Commissioning (basic settings of controls)