9.6.
Termination resistor: connect
✔
Switch [S1] is only available for line topology. For loop topology, termination is
done automatically; therefore a switch for the termination resistor is not required.
✔
This setting is only required if the actuator is the last fieldbus device.
✔
The termination resistor can only be set via switch [S1] and not via the software.
→
Switch on the termination resistor for channel 1 using switch [S1] (standard).
Information: As soon as the termination resistors are switched on, the
connection to the next fieldbus device (to XK3) is automatically interrupted to
avoid multiple terminations.
Table 13: Switch [S1] functions
Fieldbus termination OFF; sliding switch at white dot (pin 1)
(delivery state)
OFF
Fieldbus termination ON
ON
9.7.
Output speed: set
Output speed at output drive is defined by the motor speed.
Setting via switches
Condition: Switch [S5] is in position OFF (hardware mode)
Figure 21: Speed switch
[S8]
Output speed
Default value: depending on the order
Setting range: 9 steps (refer to table)
30
SVM 05.1 – SVM 07.5 / SVMR 05.1 – SVMR 07.5
Commissioning (basic settings of controls)
Modbus RTU