Figure 28: Field system settings
This menu is used to adapt the parameters of the selected SIMA² network. It is
possible to configure, for example, the network topology, the redundancy settings
or the HSA. The
Network “number”
button in the left top corner is used to switch
between networks.
After configuration, selection via the three-dot More Options icon in the top right
corner and the
Commissioning
entry or via the main menu is used to navigate to the
desired menu item:
Figure 29: Field system commissioning
Information
For hot standby system redundancy, commissioning must be made via SIMA A.
In this menu, there are two buttons for commissioning. In case of a line topology,
first use the
Update live list
button. Once the live list has completely been updated
and displays 100 %, the
Read loop configuration
button must be clicked next. The
100 % display indicates that the procedure has been successfully completed. The
Network “number”
button is used to perform this procedure for all networks. As soon
as all networks have been correctly configured and all actuators found, the settings
must be saved.
For this, use the disc symbol
in the top right corner.
29
SIMA² Master Station
MODBUS RTU, MODBUS TCP/IP to DCS
Commissioning