For the electrical connection at wall bracket [3], the terminals are made as crimp
connections.
-
Use a suitable four indent crimp tool for crimping.
-
Cross sections for flexible wires:
-
Control cables: max. 0.75 to 1.5 mm²
-
Mains connection: max. 2.5 to 4 mm²
●
When using connecting cables, e.g. of the heater or switch, requiring direct
wiring from the actuator to the XK customer plug (XA-XM-XK, refer to wiring
diagram), these connecting cables must be subject to an insulation test in
compliance with EN 50178. Connecting cables of position transmitters (EWG,
RWG, IWG, potentiometer) do not belong to this group. They may not be sub-
jected to an insulation test.
6.3.2.
Parking frame
Figure 35: Parking frame, example with AUMA plug/socket connector and cover
Application
Parking frame for safe storage of a disconnected plug or cover.
For protection against touching the bare contacts and against environmental
influences.
6.3.3.
DS intermediate frame for double sealing
Figure 36: Electrical connection with DS intermediate frame
[1]
Electrical connection
[2]
DS intermediate frame
Application
When removing the electrical connection or due to leaky cable glands, there is a
potential risk of ingress of dust and water into the housing. This is prevented
38
SAV 07.2 – SAV 16.2 / SARV 07.2 – SARV 16.2 Control unit: electronic (MWG)
Electrical connection