6.2.3.
Terminal compartment (for mains connection): close
Figure 29: Terminal compartment: close
[1A]
Cover (version S)
[1B]
Connection housing (SD version)
[2]
Screws
[3]
O-ring
[4]
Screws for socket carrier
[5]
Socket carrier
[6]
Cable gland (not included in delivery)
[7]
Blanking plug
Short-circuit due to pinching of cables!
Risk of electric shock and functional failures.
→
Carefully fit socket carrier to avoid pinching the cables.
1.
Insert the socket carrier [5] into the cover [1A] or connection housing [1B] and
fasten with screws [4].
2.
Clean sealing faces of cover [1A] or connection housing [1B] and housing.
3.
Check whether O-ring [3] is in good condition, replace if damaged.
4.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5.
Fit cover [1A] or connection housing [1B] and fasten screws [2] evenly crosswise.
6.
Fasten cable glands and blanking plugs applying the specified torque to ensure
the required enclosure protection.