Electronic control unit
Magnetic limit and torque transmitter (MWG)
Turns per stroke: 1 to 500 (standard) or 10 to 5,000 (option)
Non-Intrusive setting
Via actuator controls
Position feedback signal
Via actuator controls
Torque feedback signal
Blinking signal via actuator controls
Running indication
Resistance type heater with 5 W, 24 V AC
Heater in switch compartment
Service conditions
Indoor and outdoor use permissible
Use
As required for grease use as lubricant (standard)
When using oil instead of grease within the actuator gear housing, perpendicular mounting position is
specified whereby the flange is pointing downward.
Mounting position
≤
2 000 m above sea level
> 2,000 m above sea level on request
Installation altitude
Refer to actuator name plate
Ambient temperature
Up to 100 % relative humidity across the entire permissible temperature range
Humidity
IP68 with AUMA 3-phase AC motorwith AUMA 1-phase AC motors of types AE..., VE..., AC..., VC...with
AUMA 1-phase AC motors of types AE..., VE...with AUMA DC motor
Terminal compartment additionally sealed against interior of actuator (double sealed)
Enclosure protection in accordance
with IEC 60529
According to AUMA definition, enclosure protection IP68 meets the following requirements:
●
Depth of water: maximum 8 m head of water
●
Continuous immersion in water: maximal 96 hours
●
Up to 10 operations during immersion
●
Modulating duty is not possible during immersion.
For exact version, refer to actuator controls name plate.
Pollution degree 4 (when closed), pollution degree 2 (internal)
Pollution degree according to IEC
60664-1
2 g, 10 to 200 Hz (AUMA NORM), 1 g, 10 to 200 Hz (for actuators with AMExC or ACExC actuator
controls)
Resistant to vibration during start-up or for failures of the plant. However, a fatigue strength may not be
derived from this. Not valid in combination with gearboxes.
Vibration resistance according to
IEC 60068-2-6
KS: Suitable for use in areas with high salinity, almost permanent condensation, and high
pollution.
Standard:
Corrosion protection
KX: Suitable for use in areas with extremely high salinity, permanent condensation, and
high pollution.
KX-G: Same as KX, however aluminium-free version (outer parts)
Options:
Double layer powder coating
Two-component iron-mica combination
Coating
AUMA silver-grey (similar to RAL 7037)
Standard:
Colour
Available colours on request
Option:
AUMA multi-turn actuators meet or exceed the lifetime requirements of EN 15714-2. Detailed information
can be provided on request.
Lifetime
< 72 dB (A)
Sound pressure level
Further information
ATEX Directive 2014/34/EU
Machinery Directive 2006/42/EC
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
RED Directive 2014/53/EU
EU Directives
74
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit: electronic (MWG)
Technical data
ACExC 01.2 Non-Intrusive Modbus TCP/IP