Table 26: Default setting of the IP interface:
Static IP
Address Type
192.168.255.1
Static IP Address
255.255.0.0
Subnet Mask
192.168.0.1
Default Gateway
If required, only the IP interface must be adapted to the requirements of the Modbus
TCP/IP network. All further settings of the Modbus TCP/IP gateway (particularly the
port settings) are set as default in the factory.
10.4.
Test run
Only perform test run only once all settings previously described have been
performed.
10.4.1.
Direction of rotation at hollow shaft/stem: check
Figure 71: Direction of rotation of the hollow shaft/stem for operation in direction
CLOSE (“clockwise closing” version)
[1]
Threaded plug
[2]
Seal
[3]
Hollow shaft
[4]
Protective cap for stem protection tube
[5]
Stem
[6]
Stem protection tube
Valve damage due to incorrect direction of rotation!
→
If the direction of rotation is wrong, switch off immediately (press STOP).
→
Eliminate cause, i.e. correct phase sequence for cable set wall bracket.
→
Repeat test run.
Check direction of rota-
tion
1.
Move actuator manually to intermediate position or to sufficient distance from
end position.
2.
Depending on the version: Unscrew threaded plug [1] with seal [2], protective
cap [4] or stem protection tube [6].
3.
Switch on actuator in direction CLOSE and observe direction of rotation at hollow
shaft [3] or stem [5]:
➥
The direction of rotation is correct if the actuator moves in direction CLOSE
and the hollow shaft in clockwise direction, or the stem moves downward.
4.
Correctly fit/screw on threaded plug [1] with seal [2], protective cap [4] for stem
protection tube [6], fasten thread.
60
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit: electronic (MWG)
Commissioning (basic settings)
ACExC 01.2 Non-Intrusive Modbus TCP/IP