6.12 - Decommissioning and disposal
6.11.2 - Outdoor sensor
Temp.
(°C)
Resist. R
(KOhms)
Temp.
(°C)
Resist.
(KOhms)
Temp.
(°C)
Resist.
(KOhms)
Temp.
(°C)
Resist.
(KOhms)
-30
171 800
-11
61 930
8
24 947
27
11 079
-29
161 817
-10
58 880
9
23 853
28
10 645
-28
152 994
-9
56 004
10
22 800
29
10 231
-27
144 697
-8
53 280
11
21 819
30
9 804
-26
136 894
-7
50 702
12
20 879
31
9 460
-25
129 800
-6
48 263
13
19 986
32
9 101
-24
122 646
-5
45 950
14
19 137
33
8 759
-23
116 145
-4
43 769
15
18 300
34
9 434
-22
110 025
-3
41 699
16
17 565
35
8 054
-21
104 261
-2
39 739
17
16 839
36
7 749
-20
98 930
-1
37 881
18
16 151
37
7 456
-19
93 713
0
36 130
19
15 500
38
7 176
-18
88 888
1
34 453
20
14 770
39
6 909
-17
84 339
2
32 871
21
14 168
40
6 652
-16
80 047
3
31 371
22
13 590
41
6 408
-15
76 020
4
29 948
23
13 039
42
6 173
-14
72 174
5
38 600
24
12 514
43
5 947
-13
68 564
6
27 317
25
12 000
44
5 731
-12
65 153
7
26 101
26
11 535
45
5 522
In accordance with current laws, no equipment must be disposed
of without the refrigerant gas, recyclable metallic parts and the oil
contained in the compressors having been recovered beforehand.
NOTES / MAINTENANCE
Date
Intervenant
Nature de l'Opération
Charge récupérée
Charge introduite
Date
Worker
Work carried out
Refrigerant recovery
Refrigerant charge