4.2 

Connecting to Power and Replacing Power Supply 

This section lists the various warnings, cautions and notes regarding connecting to the power 

supply and replacing power supply units. 
 

 

Warning:  

To reduce the risk of electric shock or energy hazards: 

 

This equipment must be installed by trained service personnel, as defined by 

the NEC and IEC 60950-1, Second Edition, the standard for Safety of 

Information Technology Equipment. 

 

Connect the equipment to a reliably grounded Secondary circuit source. A 

Secondary circuit has no direct connection to a Primary circuit and derives its 

power from a transformer, converter, or equivalent isolation device. 

 

The branch circuit overcurrent protection for DC power supply must be rated 27 

A. 

 

 

Caution:  

If the DC connection exists between the earthed conductor of the DC supply circuit and 

the earthing conductor at the server equipment, the following conditions must be met: 

This equipment must be connected directly to the DC supply system earthing electrode 

conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC 

supply system earthing electrode conductor is connected. 

 

This equipment must be located in the same immediate area (such as adjacent 

cabinets) as any other equipment that has a connection between the earthed 

conductor of the same DC supply circuit and the earthing conductor, and also 

the point of earthing of the DC system. The DC system should be earthed 

elsewhere. 

 

The DC supply source is to be located within the same premises as the 

equipment. 

 

Switching or disconnecting devices must not be in the earthed circuit conductor 

between the DC source and the point of connection of the earthing electrode 

conductor. 

 

 

Note: 

The DC power cord is not supplied. For information, refer to the Section 

“Related Options: -48VDC Power Cables” at 

https://h20195.www2.hpe.com/v2/gethtml.aspx?docname=c04346217

 

 

 

Warnings:  

 

Both Power Supply modules (1 and 2) must be connected. Ensure that you 

connect each one to a different AC power supply source. Two Power Supplies 

provide 1+1 power load-sharing and redundancy. The AC power sockets are 

located on the device's rear panel.  

 

The two AC power sources must have the same ground potential. 

 

The device must be connected (by service personnel) to a socket-outlet with a 

protective earthing connection. 

 

Use only a certified 3-conductor power cord, supplied with the unit. 

 

Summary of Contents for Mediant 9000 Rev. B

Page 1: ...Hardware Installation Manual AudioCodes Mediant Family of Session Border Controllers SBC Mediant 9000 SBC Series Mediant 9000 Rev B Mediant 9030 Mediant 9080 Version 7 2...

Page 2: ......

Page 3: ...22 4 3 Connecting Display and Keyboard 24 4 4 Connecting Device to IP Network for 1 GbE Copper 24 4 5 Connecting Device to IP Network with SFP 26 4 6 Viewing Network Port Status 27 5 Fiber Network Car...

Page 4: ...per Physical Ethernet Port Mediant 9080 Mediant 9000 Rev B 24 Figure 4 2 Management Name per Physical Ethernet Port Mediant 9030 24 Figure 4 3 Connecting the Device to the IP Network Mediant 9080 Medi...

Page 5: ...List of Tables Table 2 1 Specifications 13 Table 3 1 Physical Dimensions 15 Table 3 2 Front Panel 15 Table 3 3 Front Panel LEDs 16 Table 3 4 Rear Panel 17 Table 3 5 Rear Panel LEDs 19 Table 5 1 Suppor...

Page 6: ...Mediant 9000 Series SBC Hardware Installation Manual 6 Document LTRT 41667 This page is intentionally left blank...

Page 7: ...this product Customer Support Customer technical support and services are provided by AudioCodes or by an authorized AudioCodes Service Partner For more information on how to buy technical support for...

Page 8: ...ly wiring Appropriate consideration of equipment nameplate ratings should be used when addressing this concern Caution Laser This device contains a Class 1 LED Laser emitting device as defined by 21CF...

Page 9: ...nfigurations Replacing Copper NIC with Fiber Network Card new section Returning to an Arbitrary Snapshot updated 41663 Logo updated note added to Returning to an Arbitrary Snapshot 41664 Updates for H...

Page 10: ...Mediant 9000 Series SBC Hardware Installation Manual 10 Document LTRT 41667 This page is intentionally left blank...

Page 11: ...s based on HPE ProLiant DL360 Gen10 To identify the type of Mediant 9000 product run the show system hardware command as shown in the examples below Mediant 9080 and Mediant 9000 Rev B show system har...

Page 12: ...Mediant 9000 Series SBC Hardware Installation Manual 12 Document LTRT 41667 This page is intentionally left blank...

Page 13: ...ssis Type 1RU System CPU 2 x 12 Cores 2 6 GHz 19 25MB Cache 2 x 8 Cores 2 1 GHz 11MB Cache Memory 96 GB DDR4 2666 PC4 21300 32 GB DDR4 2666 PC4 21300 Network Orderable configuration 8 x 1 GbE ports an...

Page 14: ...Mediant 9000 Series SBC Hardware Installation Manual 14 Document LTRT 41667 This page is intentionally left blank...

Page 15: ...Environmental Operational 10 to 35 C 50 to 95 F 3 2 Front Panel The device features an 8 SFF Small Form Factor cage for standard internal storage hard drives The device s front panel is shown in the...

Page 16: ...on LED and system power LED Solid green System on Flashing green Performing power on sequence Solid amber System in standby Off No power present 3 Health LED Solid green Normal Flashing green iLO is r...

Page 17: ...3 Rear Panel Mediant 9080 Mediant 9000 Rev B Figure 3 4 Rear Panel Mediant 9030 Table 3 4 Rear Panel Item Description Mediant 9080 Mediant 9000 Rev B Mediant 9030 1 Slot 1 Quad 1 GbE copper ports Slo...

Page 18: ...tem Description Mediant 9080 Mediant 9000 Rev B Mediant 9030 7 Unsupported NIC ports dust covered Quad 1 GbE copper ports Note These ports can be used only for signaling SIP OAMP and HA Maintenance 8...

Page 19: ...d remotely Off Identification is deactivated 2 iLO 5 standard Right LED NIC activity status Solid green Activity exists Flashing green Activity exists Off No activity exists Left LED NIC link status S...

Page 20: ...20 Document LTRT 41667 Item Description Status 5 Quad 1 GbE copper ports Right LED NIC activity status Solid green Activity exists Flashing green Activity exists Off No activity exists Left LED NIC li...

Page 21: ...he following safety instructions Elevated Operating Temperature If installed in a closed or multi unit rack assembly the operating ambient temperature of the rack environment may be greater than room...

Page 22: ...terminal bar or bus to which the DC supply system earthing electrode conductor is connected This equipment must be located in the same immediate area such as adjacent cabinets as any other equipment...

Page 23: ...ire 1 negative polarity Red Wire 2 positive polarity Note When connecting both Power Supply modules the two AC power sources must have the same ground potential Warning The device must be connected by...

Page 24: ...connection to intra building or unexposed wiring or cabling only The intra building ports of the equipment must not be metallically connected to interfaces that connect to the Outside Plant OSP or its...

Page 25: ...for media traffic To connect the device to the IP network Use an Ethernet cable to connect an RJ 45 network port on the server s rear panel to the LAN Figure 4 3 Connecting the Device to the IP Networ...

Page 26: ...tic Cable can cause distortion and signal losses 2 Ensure the minimum bending radius recommended by the Fiber Optic Cable supplier 3 Incoming optic cabling from the network infrastructure can originat...

Page 27: ...9 DOWN 1 igb rx zc 3 GE_3 f4 ce 46 a5 3f 9a DOWN 1 igb rx zc 4 GE_4 f4 ce 46 a5 3f 9b DOWN 1 igb rx zc 5 GE_5 f4 ce 46 a5 4f 98 DOWN 1 igb rx zc 6 GE_6 f4 ce 46 a5 4f 99 DOWN 1 igb rx zc 7 GE_7 f4 ce...

Page 28: ...Mediant 9000 Series SBC Hardware Installation Manual 28 Document LTRT 41667 This page is intentionally left blank...

Page 29: ...LX Quad SFP 10G with SX transceivers Quad SFP 10G with SX transceivers 4 x 1 GbE Copper 8 x 10G SFP SX Note The Network cards Quad SFP 10G with LX transceivers and Quad SFP 10G with SX transceivers m...

Page 30: ...Mediant 9000 Series SBC Hardware Installation Manual 30 Document LTRT 41667 This page is intentionally left blank...

Page 31: ...using CLI 1 Use the VGA monitor and keyboard to connect to the CLI management interface 2 At the prompt type the username default is Admin case sensitive and then press ENTER Username Admin 3 At the p...

Page 32: ...10 network dev 0 tagging tagged network dev 0 exit 10 At the prompt type exit to complete the configuration 11 At the prompt make sure that port 1 is connected Link is UP using the show network physic...

Page 33: ...iant 9000 Series SBC 6 2 Licensing the Device The device is supplied with a pre installed software and License Key Use the pre installed License Key to enable the call capacity and features that you o...

Page 34: ...Mediant 9000 Series SBC Hardware Installation Manual 34 Document LTRT 41667 This page is intentionally left blank...

Page 35: ...tware SBC from ISO Image The device is pre installed on the device s server In case a clean installation of the device s software is required you should download the latest installation image from the...

Page 36: ...ounting ISO Image from Remote Console 4 Reset the server from the Remote Console by using for example the Power Switch button The server boots from the Remote Console see Figure A 2 and the Mediant SE...

Page 37: ...stallation progress Figure A 4 Installation in Progress 6 Wait for the Complete prompt notifying you when installation is complete to be displayed Installation takes approximately 20 minutes Figure A...

Page 38: ...Mediant 9000 Series SBC Hardware Installation Manual 38 Document LTRT 41667 This page is intentionally left blank...

Page 39: ...es SBC B Rescue Options The device features a System Snapshots mechanism that provides the capability of returning the system to a previous state The mechanism may be used as a rescue option if a syst...

Page 40: ...udiocodes com 2018 AudioCodes Ltd All rights reserved AudioCodes AC HD VoIP HD VoIP Sounds Better IPmedia Mediant MediaPack What s Inside Matters OSN SmartTAP User Management Pack VMAS VoIPerfect VoIP...

Reviews: