background image

 

 AUBER INSTRUMENTS

    

 

 

 

 

 

 

            

WWW.AUBERINS.COM 

 

2021.01             

 

 

               P3/6 

will take effect without the need for pressing the SET key. Figure 5 shows the 
flow chart of the parameters.  
Note:  If  the  controller  is  locked  (see  4.13),  only  limited  parameters  (or  no 
parameters) can be changed. 
 

4.2 Parameter Name, Range and Initial Setting 

 

4.2.1 Alarm parameters 

This controller has two alarm outputs: Alarm 1 (AL1, NO relay) and Alarm 2 
(AL2, NO relay). Two red alarm indicators are located on the front panel: AL1 
and AL2. Alarm 1 and AL1 indicator are synchronized. Alarm 2 and AL2 
indicator are synchronized. When the AL1 (AL2) indicator is ON, alarm 1 (alarm 
2) relay pulls in. When the AL1 (AL2) indicator is OFF, alarm 1 (alarm 2) relay 
drops off.   
 
Each alarm is set by three parameters: 

ALP, AL 

and

 Hy

. ALP1, AL1 and Hy1 

are for Alarm 1. ALP2, AL2 and Hy2 are for Alarm 2. Alarm 1 can be set as 
either temperature alarm (ALP1 = 1 ~ 4) or timer alarm/output (ALP1 = 0). 
Alarm 2 can only be used for temperature alarm (ALP2 = 1 ~ 4). See ALP 
definition below.   

 

 

ALP

 defines the type of alarm.  

ALP = 0, timer alarm/output (alarm 1 only) 
ALP = 1, high limit temperature alarm.  
ALP = 2; low limit temperature alarm.  
ALP = 3; deviation high temperature alarm.  
ALP = 4, deviation low temperature alarm. 
 
Note: When ALP1 is set to 0 (for timer output), parameter AL1 and Hy1 are not 
in use. Only ALP1 can be set to 0. ALP2 = 0 is not functional for SWA-2451B.    
 

AL

 is for the alarm temperature setting. When alarm is set for high/low limit 

alarm, its value is the temperature that alarm will turn on. When alarm is set for 
high/low deviation alarm, its value indicates that the alarm will turn on when 
temperature is deviated AL degree from the set temperature (SV). Note: when 
alarm is set to deviation alarm (ALP1 / ALP2 is set to either 3 or 4), AL1 / AL2 
can only be set to 100 as maximum. 
 

Hy

 is the hysteresis band of temperature alarm. This parameter also uses for 

ON/OFF control mode (see 4.2.2 below). In heating mode, for high limit or 
deviation high alarm mode, the alarm will turn off when the temperature is Hy 
degree below alarm on setting; for low limit and deviation low alarm mode, the 
alarm will turn off when temperature is Hy degree above the alarm on setting.  
 
Example 1: ALP1 = 1 (high limit alarm), AL1 = 250, and Hy1 = 5. In this case, 
alarm 1 will turn on when temperature goes above 250 degrees (AL1) and turn 
off when temperature drop to 245 degrees (AL1-Hy1). 
 
Example 2: SV = 200, ALP1 = 4 (deviation low alarm), AL1 = 10, and Hy1 = 5. 
In this case, alarm 1 will turn on when temperature drop to 190(SV-AL1) and 
turn off when temperature goes up to 195 (SV-AL1+Hy1). 
 

4.2.2 Hysteresis Band “Hy”

  

The Hysteresis Band parameter Hy is also referred as Dead Band, or 
Differential. It permits protection of the on/off control from high switching 
frequency caused by process input fluctuation. Hysteresis Band parameter is 
used for on/off control, as well as auto-tune process. For example: When 
controller is set for on/off heating control mode, the output will turn off when 
temperature goes above SV+ Hy and on again when it drops to below SV-Hy. 
 

4.2.3 At (Auto-tuning) 

The auto-tuning function (also called self-tuning) can automatically optimize the 
PID parameters for the system. The auto-tuning function will use the on/off 
mode to heat up the system until it passes the set point. Then let it cool down. It 
will repeat this about three times. Based on the response time of the system, 
the built-in artificial intelligence program will calculate and set the PID 
parameters for the controller. If your system has a very slow response, the auto 
tuning could take a long time. 

AT start

AT calculation

AT end

ON

OFF

ON

OFF

ON/OFF

PID 

Figure 4. Auto tuning

SV

PV

 

To activate auto-tuning, enter the parameter setting mode, set At = ON. The 

“AT”

 LED on the left lower corner of the controller will light up. Auto-tune will 

finish when the AT LED turns off. The newly calculated PID parameters are set 
and used for the system. Please note that auto-tuning is only for PID control 
mode. There is no need for auto-tune when using ON/OFF mode (when P = 0).  
To stop the auto-tuning, enter the parameter setting mode, set At = OFF. Then, 
the previous PID parameters values are resumed. 
 

Hy2

1

.

0

Figure 5. System setup flow chart.

SET 3S

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

SET

AL1

999

.

9

ALP 1
Alarm 1 Definition

ALP 2
Alarm 2 Definition

Cool
Cooling Control

OUTH
Output High Limit

Lock
Configuration Privilege

Sn
Input Type

OPA
Output Mode

CF
Display Unit

DIH
Input High Limit

DIL
Input Low Limit

SC

0

.

0

P

15

.

0

I

240

D

30

AT

OFF

t

10

Hy1

1

.

0

DP

1

ALP2

0

COOL

OFF

Hy

1

.

0

AL2

0

SET

SET

SET

outh

100

LOCK

0

ALP1

0

85

.

5

10

AL1
Alarm1 Setting

AL2
Alarm2 Setting

SC
Input Offset

P
Proportional Constant

I
Integral Time

D
Derivative Time

At
Auto Tune

T
Cycle Time

Hy
Hysteresis Band

Hy 1
Alarm 1 Hysteresis Band

Hy 2
Alarm 2 Hysteresis Band

dP
Decimal Point Position

Sn

k

OPA

0

Dil

0

dih

999

.

9

cf

c

Time

SET

SET

SET

SET

SET

PV

 

 
 
 
 
 
 
 
 
 

Reviews: