9.  Place access door on lower flange lining holes in door up  
 

with pins in flange. Carefully close the door while aligning  

 

flue outlet with flue opening and pressure switch tube with  

 

plastic bushing opening, securely screw door in place with  

 

fastener already installed in door.

10. The appliance must be disconnected from the gas supply  
 

piping system during any pressure testing of the system at  

 

test pressures in excess of ½ psi. The appliance must be  

 

isolated from the gas piping system during any pressure  

 

testing at test pressures equal to or less than ½ psi.  

 

 

Pressure inlet to valve, 13” W.C. maximum, 11” W.C.    

 

minimum. Pressure at outlet of valve is factory set at       

 

10” W.C.

11. Gas Manifold pressure tap on burner assembly.

 

The gas manifold pressure at this tap

 

is 9” w.c. =/- 0.5” w.c. for both the

 

OD50 and the OD50CW models.

12. Turn on the gas and check the water heater and all  

 

 

connections for gas leaks with a leak detecting solution.

13. Turn on water supply line and check for water leaks.

PressUre relIef vAlve

THis valve is a safeTy comPonenT anD musT 
noT be removeD for any reason oTHer THan 
rePlacemenT.

 This water heater is equipped with a pressure 

relief valve that complies with the standard for Relief Valves and 
Automatic  Gas  Shutoff  Devices  for  Hot  Water  Systems,  ANSI 
Z21.22 CSA 4.4.

This valve protects against excessive water expansion only. 

This water heater has separate and dedicated protection for 
excessive heat.
If you use a discharge line, do not use a reducing coupling or 
other restriction smaller than the outlet of the relief valve. Allow 
complete drainage of both valve and line.

for rePlacemenT ParTs:

•  DO NOT install anything less than a pressure relief valve    
  certified by a nationally recognized testing laboratory  

 

  that maintains periodic inspection of product of listed  

 

  equipment or materials, as meeting requirements for Relief  
  Valves and Automatic Gas Shutoff Devices of Hot Water   
  Supply Systems, ANSI Z21.22 CSA 4.4. Valve must have   
  maximum set pressure 

not to exceed 100 psi.

•  Install replacement valve into opening provided and  

 

  designated for this purpose on water heater.
•  Installation must conform with local codes or in the  

 

  absence of local codes, Standard on Recreational  

 

  Vehicles, ANSI A119.2 or CAN/CSA-Z240RV.

WirinG insTrucTions

The appliance, when installed, must be electrically grounded 
in accordance with local codes or, in the absence of local 
codes, with the national electrical code, ansi/nfPa 70 
and/or the csa c22.1, canadian electrical code.

It is required that the unit be connected through a switch that is 
connected directly to a 12V DC battery or to the filtered side of 
an AC/DC converter. Avoid unfiltered “linear” voltage sources. 
Use a minimum of 18 gauge wire, UL and CSA Listed. Refer 
to the 

Wiring Diagram

. Install a remote switch in a convenient 

location. Position the wall plate with the letters up. Before 
making the connections, turn the switch to the OFF position.

RED is 12V DC Positive power IN.
GREEN is 12V DC Ground.
BLUE is 12V DC Pos. Lockout Lamp Signal.

(See illustration of typical switch configuration)

m

 

warning

 fIre AnD/Or exPlOsIOn

•  DO NOT use matches, candles or other sources of ignition  
  when checking for gas leaks.

m

 

warning

 exPlOsIOn

•  DO NOT place a valve, plug or reducing coupling on outlet  
  part of pressure temperature relief valve.

m

 

warning

 sCAlDInG InjUry

•  Valve is not serviceable, it must be replaced.
•  Tampering with valve will result in scalding injury.
•  Tampering with valve will void warranty.

m

 

caution

 eleCTrICAl DAMAGe

•  Label all wire prior to disconnection when servicing controls.  
  Wiring errors can cause improper and dangerous operation.
•  Verify proper operation after servicing.

BLUE FROM W.H.
(LOCK-OUT LAMP)

+12 VDC

GAS- ORANGE FROM W.H.

Summary of Contents for OD50

Page 1: ...s Btu 01__________ Generation CW______ Cold Weather Kit m critical installation warnings Install in recreation vehicles only RV s are recreation vehicles designed as temporary living quarters for recreation camping or travel use having their own power or towed by another vehicle All combustion air must be supplied from outside the RV and all products of combustion must be vented to outside the RV ...

Page 2: ...rmined and is being installed at the OEM prior to erecting the walls NOTE Parts bagged and included with the unit in the box are the corner filler brackets and push on water line connectors 1 Locate the water heater on the floor of the coach at pre determined location The unit must be permanently supported at the same level as the bottom of the sidewall cutout by the floor or a raised floor 2 To i...

Page 3: ...periodic inspection of product of listed equipment or materials as meeting requirements for Relief Valves and Automatic Gas Shutoff Devices of Hot Water Supply Systems ANSI Z21 22 CSA 4 4 Valve must have maximum set pressure not to exceed 100 psi Install replacement valve into opening provided and designated for this purpose on water heater Installation must conform with local codes or in the abse...

Page 4: ... COLD PACK OPTIONAL IGN CONT SPARK SENSE WIRING SCHEMATIC GREEN GREEN RED RED PURPLE BROWN BROWN RED RED RED PURPLE RED RED BLUE BLUE LOCKOUT LAMP OPTIONAL MPD 90211 m CAUTION FIRE DO NOT smoke or have any flame near an open faucet GENERAL INFORMATION LP and Water system must be turned on Have gas pressure tested periodically Should be set at 11 inches of water column with three appliances running...

Page 5: ...warm ranging from 70 F to 90 F it is recommended that the modulating valve adjustment be placed in the MIN position This reduces the gas input of the heater to keep the water temperature from getting too hot with high incoming water temperature Winter Operation During the winter months when incoming water temperatures are cooler ranging from 45 F to 70 F it is recommended to place the modulating v...

Page 6: ...ulting the trouble shooting guide If problems still persist contact Atwood or an authorized service center Only a qualified technician should do any work involving the gas system A periodic visual check of the burner flames should be done by observing the flame through the peep hole in the heat exchanger There should be blue flame with minimum or no yellow tipping Burner maintenance should be perf...

Page 7: ...inter summer valve is in the proper position for the temperature of the incoming water 3 Water flow too low for incoming water temperature 5 Be sure there is a battery in the system Never connect the heater directly to a power converter Some converters have circuits that are not pure DC This can cause malfunctions or damage to the heater and is not covered by warranty 6 Be sure that no water mixin...

Page 8: ...lacement of burner orifices c cleaning or adjustment of burner assembly d cleaning or adjustment of flue e adjustment of pressure relief valve 4 In the event of a warranty claim the owner must contact in advance either an authorized Atwood Service Center or the Atwood Service Department Warranty claim service must be performed at an authorized Atwood Service Center can be found online www atwoodmo...

Page 9: ... ont pas été réparées L installation et la réparation doivent être effectuées par un installateur qualifié une agence de service ou le fournisseur de gaz Explication du numéro du modèle OD_____________________ À la demande On demand 50________________ Entrée en milliers de BTU 01__________ Génération CW______ Kit de temps froid m AVERTISSEMENTS CRITIQUEs SUR L INSTALLATION À installer dans les véh...

Page 10: ... y a d autres méthodes approuvées comme celles dans le coffre à bagages ou le boîtier encastré Pour toute question supplémentaire veuillez consulter votre vérificateur sur place votre directeur de compte ou le service à la clientèle Atwood Avant de commencer assurez vous que l emplacement approprié a été déterminé et installé par le FEO avant l érection des murs REMARQUE Les pièces mises en sac et...

Page 11: ...e l interrupteur en position OFF ROUGE est le courant positif d entrée de 12 V c c VERT est la mise à la terre de 12 V c c BLEU est le signal de verrouillage de 12 V c c positif Voir l illustration de la configuration de commutation type 7 Pour prévenir les fuites d eau calfeutrez soigneusement le pourtour arrière des brides et sur les fentes pliées et perforées Calfeutrez le pourtour de l ouvertu...

Page 12: ... ouvrez le robinet d eau chaude de l évier de cuisine pendant plusieurs minutes avant d utiliser tout appareil électrique relié au système d eau chaude Si de l hydrogène gazeux est présent vous allez probablement entendre des sons tels que l air qui s échappe par le tuyau au moment où l eau commence à couler 1 Mettre en pression le système d eau en tournant sur la pompe ou la pression d eau de vil...

Page 13: ...débit dans les robinets et ou des pommes de douche Éliminer les restricteurs pour de meilleures performances 4 Propane pression du système de gaz doit être 11 W C en cours de fonctionnement Assurez vous que les réservoirs de propane comportent beaucoup de gaz et sont correctement régulés Cela doit être vérifié par un technicien agréé Atwood Si le problème persiste s il vous plaît contacter le cent...

Page 14: ... 90290 LISTE DES PIÈCES DU CHAUFFE EAU DÉPANNAGE La plupart des problèmes sont facilement résolus en consultant le guide de dépannage Si le problème persiste veuillez contacter Atwood ou un centre de service agréé Seul un technicien qualifié devrait effectuer tout travail impliquant le système de gaz Une vérification périodique visuelle des flammes du brûleur devrait être faite en observant la fla...

Page 15: ...avec le terminal seulement 5 Assurez vous que l alimentation du ventilateur a 12 volts lorsque de l eau coule et qu il n y a pas d obstacles dans le conduit d air 6 Assurez vous que mano contact est clôturé par la vérification la tension à travers des terminaux devrait être de 0 volts si lisant 12 volts vérifient l obstruction de conduite ou l obstruction dans la ligne de sens tuyauterie L eau ne ...

Page 16: ...rais d essence de téléphone de déplacement d hébergement le manque à gagner ou les dommages matériels Certains États n autorisent pas les exclusions ou les restrictions des dommages accessoires ou consécutifs par conséquent il est possible que les restrictions ou les exclusions précédentes ne s appliquent pas à vous 10 Les garanties implicites se limitent à une période de deux 2 ans Certains États...

Reviews: