19
UMD-SRB01
Version 4
Resetting the System
To “SET” the system for the very first time is the same procedure as each time
you need to “RESET” the system, and that is as follows.
n
Check that all faults are cleared and that there is no reason why the lift
cannot be put back into service. i.e. reason for brakes to be deployed has
been rectified.
(If there are faults rectify them first.)
n
Check that there is power at the controller i.e. “Control Voltage” LED
is illuminated.
(If there is no power test fuses etc, find out why)
n
Check that there are no brakes displaying that they are already “SET”.
(If they are already displaying “set” then check internal switches of the
rope brake)
n
Insert the key into the reset/run/bypass switch.
n
Turn the key to the reset position and leave it there whilst the brakes are reset.
(A sounder will beep to remind you that the system is in reset mode, also the
lift will be prevented to run until the brakes are reset and the key is returned
to run position.)
Warning the safety devices controlled by this controller are bypassed
while the key is in this position.
n
The rope brakes will require lifting into position, and then they will hold there.
n
System is now SET.
n
Return key to central RUN position.
Normal Operation