9
1.5
CONTROL PANEL
1.5.1
ATTACK DPX STANDARD
The wood gasifying boiler "ATTACK DPX STANDARD" is controlled by the boiler and the flue gas
thermostat.
1 – Safety thermostat
with reset
2 – Fuse
3 – Main switch
4 – Flue gas thermostat
5 – Boiler thermostat
6 – Thermo-manometer
Description:
1.
Safety thermostat with reset – boiler protection against overheating (after exceeding the
temperature of 110 °C is the boiler disconnected from electricity mains). After the
temperature decreases below 85 °C, it is necessary to undo the reset cover and to press the
restart button manually.
2.
Fuse – boiler protection against short circuit
3.
Main switch – boiler start and stop for the case of need
4.
Flue gas thermostat – the fan is stopped after the flue gas temperature decreases below
the adjusted value
ATTENTION!
Set this thermostat to 0 °C by heating up. After the fuel starts to burn, set the
flue gas thermostat to the „Operation“ position. When the temperature decreases under
the adjusted value, the exhaust fan is stopped. To start the fan again, set the lower
temperature value on the thermostat. The optimal setting for operation will be found by
experience.
5.
Boiler thermostat – serves to set the max. temperature of water in the boiler (After
exceeding the adjusted temperature is the fan stopped and the boiler works at min.
output. After the temperature decreases below the adjusted value, the fan is started again
and the boiler works at max. output).
6.
Thermo-manometer – shows the output temperature of water from the boiler and the
operating pressure
Pull rod of the chimney flap – serves to close and to open the heat up flap (always by opening
the feeding door)
Lever for exchanger cleaning – serves to clean the holes of the exchanger