49
4.31
FAULTS AND ERRORS WITH THE SYSTEM ATTACK DPX
LAMBDA
It is not possible to heat in the boiler in case of the following errors and warnings:
the red display 3 shines (errors), operation in the wood boiler is not possible
the red display 3 flickers (warning), correct boiler operation is not possible. The text
automatically disappears after the cause of error is solved.
The boiler operation under the emergency mode is possible, if:
the yellow display 2 (warning) lights
All the emergency programmes in the options of the regulator are automatically explained and
they serve for a short-term operation of heating. Thereby:
It is recommended to remove the error immediately!
If the operation under an appropriate emergency program takes too long, it may come to the
damage of the chimney and the boiler and to the consequent loss of the guarantee.
Start of the emergency thermostat (error)
STB is started
reset
Temperature in the
boiler ( °C)
Cause:
The temperature in the boiler is > 95 °C
because of too big amount of fuel, power
shortage, error by heat outtake (or in the
circuit pump)
Indicator light 3 red
Shines
Solution:
Load less fuel! Check the heat outtake!
Reset:
Undo the cover (8) and press the STB button
placed underneath when the text „boiler
temperature 85 °C “ is displayed! The error is
automatically removed within few seconds.
Emergency program:
Actions of the
regulator:
NO
Automatic boiler stop.
By the boiler temperature > 86 °C, the
outtake of the surplus heat is stopped
V1 and V2 are adjusted after the setting is
done
If the error repeats, it is necessary to inform the service
technician.
Incorrectly measured values of the boiler temperature (error)
Incorrectly
measured boiler
temperature
Boiler temperature
( °C)
Cause:
Indicator light 3 red
Measured values < –20 °C, or > +150 °C
Shines
Solution:
Reset:
Check the sockets and conductors! Replace
the sensors, is necessary!
Automatically after the error is removed
Emergency program:
Actions of the
regulator:
NO
Automatic stop of the flue gas fan and the
circuit pump
V1=0 %, V2= min. 25 % open