SETTING FOR COMMISSION OF THE ATTACK DPX LAMBDA
The device can be commissioned, when the minimum requirements for the testing operation or
heating are fulfilled (see the chapter 1.2). Then it is necessary to make the following settings.
Settings by using the code of the service technician
The button „
←
“ enables to enter into the menu of Options, where the submenu „settings” can be
changed by the „+“ and „–“. The button „
←
“ is used to confirm the selection.
Exit from the submenu comes automatically after selecting the „supply valve“ by the button „
←
“.
Then is the display automatically switched into the operating mode. If no button is pressed
during 1 minute, the display is automatically switched to the operating mode.
Settings:
Menu
Submenu
Indication
Information
Test of device
Safety test
Setting
Entering the code
---
Set the code by the „+“ button. The random
number is displayed on the left side. Enter the
code and confirm by the button „
←
“. The code
for service technician is available by producer.
01 :Language
German DE
English GB
Spanish ES
Italian IT
French FR
Swedish SE
Polish PL
Slovak SK
Czech CZ
Dutch NL
Danish DK
Hungarian HU
Slovenian SI
Function: Setting the national language
02: Boiler setting
°C
85
Function: Set the temperature in the boiler
Producer: 85 °C
Range for setting: 75–85 °C
03: TAG setting
°C
180
Function: Setting the flue gas temperature
(nominal boiler output 180 °C).
Producer: 180 °C
Range for setting: 110–240 °C
Note: TAG = flue gas temperature
04: O
2
setting
% 6,0
Function: Setting the O
2
value for burning 6 %
Producer: 6,0 %
Range for setting: 4,0–8,0 %
05 : TAD start
K 60
Function: To get the sufficient output of
heating before closing the feeding door
Producer: 60K
Range for setting: 25K d – 125K
Note: TAD = temperature difference.
Difference between the flue gas temperature
and the temperature in the boiler.