WOOD GASIFYING BOILER
ATTACK DPX
STANDARD / PROFI / LAMBDA
INSTRUCTIONS FOR USE
Page 1: ...W W W A T T A C K S K WOOD GASIFYING BOILER ATTACK DPX STANDARD PROFI LAMBDA INSTRUCTIONS FOR USE...
Page 2: ...NNECTED IN SERIE 19 3 3 5 WOOD GASIFYING BOILER HEATING CIRCUIT WARMING OF THE COMBINED ACCUMULATION TANK 20 3 4 REGULATOR CONTROL AND OPERATING MODES 21 3 5 SETTING THE USER PARAMETERS 22 3 6 SETTING...
Page 3: ...F PARTS 45 4 23 BOILER CONNECTION 46 4 24 OPERATION WITH ACCUMULATION TANKS 46 4 25 BOILER PROTECTION AGAINST OVERHEATING 47 4 26 TRANSPORT HANDLING AND STORING 47 4 27 INSTRUCTIONS FOR PRODUCT DISPOS...
Page 4: ...one equalization tank with the volume of approximately 25 l 1 kW of the boiler s output By the operation with lower output summer operation and D H W preparation it is necessary to heat the boiler up...
Page 5: ...is damaged it must be replaced with a special cable available by producer or by a service technician Be careful by work with device The Lambda sensor works by high temperatures 300 C and there is a d...
Page 6: ...professional maintenance reliable service 1 1 GENERAL DESCRIPTION Wood gasifying boiler ATTACK DPX Name WOOD GASIFYING BOILER ATTACK DPX 15 25 30 35 40 45 IN VERSION STANDARD PROFI LAMBDA Type ATTACK...
Page 7: ...oiler class 5 5 5 5 5 5 Flue gas temperature by nominal output C 160 165 170 180 170 180 Flue gas flow by nominal output kg s 0 014 0 018 0 020 0 022 0 025 0 028 Maximum noise level dB 65 65 65 65 65...
Page 8: ...G 6 4 G 6 4 G 6 4 G 6 4 G 2 G 2 KEY 1 Boiler body 5 Suction fan 9 Control panel 13 Flow connection 2 Upper cover 6 Chimney 10 Drain valve 14 Return connection 3 Feeding door 7 Flap of primary air 11 C...
Page 9: ...low the adjusted value ATTENTION Set this thermostat to 0 C by heating up After the fuel starts to burn set the flue gas thermostat to the Operation position When the temperature decreases under the a...
Page 10: ...r pressing the button for the first time The boiler is started after the button is pressed again then it is possible to heat it up or to refill the fuel Also other settings can be done by this button...
Page 11: ...fication by using the exhaust fan that sucks the flue gas from the boiler The boiler body is welded from the steel plates of 6 mm thickness In the feeding chamber there is a fireproof nozzle with long...
Page 12: ...fault There will be no more condensate after heating for a longer time In the case that the smaller wooden waste is being burned it is necessary to check the flue gas temperature which should not exc...
Page 13: ...bed chimney draught the boiler works up to 70 of its output even without the fan Electromechanical boiler regulation The boiler is regulated by the boiler thermostat placed on a boiler panel which con...
Page 14: ...CK PROFI PID is a sophisticated regulator for wood gasifying boilers DPX There is an improvement of regulation the flue gas temperature is controlled by the PID The regulator can control 1 Rotations o...
Page 15: ...e 8 setting the boiler temperature 9 button to enter into the information menu service menu and confirmation of parameters 10 icon for fan operation 11 operation of the pump for D H W or for accumulat...
Page 16: ...pull it out from the control panel through the prepared plastic bushing This action can be performed only by a qualified person or by a person trained by producer The regulator is set by production f...
Page 17: ...17 3 3 2 WOOD GASIFYING BOILER HEATING CIRCUIT WARMING OF D H W Parameter setting for the hydraulic scheme 3 2 ur ur1 for priority charging of the D H W tank ur ur2 for paralel charging the D H W tank...
Page 18: ...18 3 3 3 WOOD GASIFYING BOILER HEATING CIRCUIT WARMING OF ACCUMULATION TANK Parameter setting for the hydraulic scheme 3 3 ur ur4...
Page 19: ...19 3 3 4 WOOD GASIFYING BOILER HEATING CIRCUIT WARMING OF ACCUMULATION TANKS CONNECTED IN SERIE Parameter setting for the hydraulic scheme 3 4 ur ur4...
Page 20: ...20 3 3 5 WOOD GASIFYING BOILER HEATING CIRCUIT WARMING OF THE COMBINED ACCUMULATION TANK Parameter setting for the hydraulic scheme 3 5 ur ur4...
Page 21: ...50 C indicates the winter operating mode when the boiler temperature is achieved 50 U indicates summer operating mode intended only for D H W preparation 50 u indicates summer operating mode when the...
Page 22: ...R SUMMER mode the winter mode is indicated by the C letter Then is the circuit pump controlled by the room thermostat and distributes the heat into the heating system The summer mode is indicated by t...
Page 23: ...0 Ph 2 Hysteresis of circuit pump 1 40 1 C 2 Pc Interval of unlock function of circuit pump 1 99 1min 2 ur4 Operation of additional output 0 4 1 4 u30 Operating temperature of D H W tank or accumulati...
Page 24: ...stopped due to the boiler temperature achieved u 6 Duration of exhaust fan blow through during this period must the fan exhaust the flue gas following the parameter n 5 r 100 Fan output by ignition t...
Page 25: ...r the D H W is prepared ur 2 Parallel charging the D H W tank similar principle as by the ur 1 just the D H W is prepared by the parallel operation of the circuit pump of the heating circuit ur 3 Unus...
Page 26: ...ler and the FUEL alarm is displayed Ar 1 parameter indicates that the additional multifunctional output will be used for error messages like boiler sensor failure overheating or fuel shortage c 240 Ad...
Page 27: ...temperature decreases under the adjusted flue gas temperature the ventilator is started again E 1 is displayed when the boiler temperature sensor fails or when it is not connected In such case is the...
Page 28: ...ulator 3 13 TECHNICAL SPECIFICATION OF THE REGULATOR Power supply 230V 10 50Hz Input not including the ventilator and pumps 4VA Range of measuring the boiler temperature 9 109 C 1 C Range of measuring...
Page 29: ...a standard function when the boiler cooling by chimney is limited Ignition with remaining coal is easier and there is less smoke by heating up When the boiler stops the flue gas fan is stopped the pr...
Page 30: ...fter 5 seconds appears the text IGNITION Prepare and ignite the fuel following the instructions on the page 11 close the feeding door partly If the bar chart is full the fuel is ignited close the door...
Page 31: ...LAY OF THE OPERATING MODE WHEN THE BOILER IS OUT OF ORDER When there is no more fuel left the boiler is automatically stopped by regulator or it can be stopped manually by the button this serves only...
Page 32: ...adjusted value of the CO2 in the flue gas CO2 Indicates the current value of the CO2 Note The fix value of the CO2 for calculation is max 20 3 Suction fan ON OFF Operating state of the fan Circuit pum...
Page 33: ...e code Set the code by the button The random number is displayed on the left side Enter the code and confirm by the button The code for service technician is available by producer 01 Language German D...
Page 34: ...ult it is regulated to the adjusted value This is a temporary solution until the fault is removed it is not a normal operating function Producer 85 Range for setting 0 100 11 V2 secondary air Air 40 F...
Page 35: ...0 33 Output reduction NO YES Select YES by the button After pressing the button is the explanation of the setting displayed and the menu is closed By selecting YES the boiler output is reduced by 20 i...
Page 36: ...int of the test Primary motor End of the test By pressing open the primary air flap By pressing close the primary air flap By pressing select the next point of the test Secondary motor End of the test...
Page 37: ...onds Then the regulator automatically switches to the operating display mode Menu Submenu Indication Information Test of device Safety test Time limit of 30 minutes for the test Safety test sec 30 Boi...
Page 38: ...r hinges The feeding door and the bottom door are fixed to the boiler body by two hinges that are connected to the door by a long joint To adjust the hinges it is necessary to remove the joint and to...
Page 39: ...t is necessary to prepare the boiler in the following way Lay some bigger wood logs 4 6 pcs on a glowing layer of fuel Close the mixing valve partly temperature of water in the boiler achieves 80 90 C...
Page 40: ...cleaning is important to ensure the permanent output and service life of the boiler The warranty is not valid if the boiler is not sufficiently cleaned and damaged 4 18 PRESCRIBED FUEL The prescribed...
Page 41: ...board from basalt felt novodur degree of flammability C1 difficult to ignite hardwood oak beech plywood werzalit hardened paper degree of flammability C2 normal combustibility softwood pine spruce ch...
Page 42: ...d values but it cannot be too high not to decrease the boiler output and interrupt the burning flame If there is too strong draught install the throttle flap into the chimney hole between the boiler a...
Page 43: ...iler protected against undercooling below 65 C and the creation of water steams acids and tars in the boiler s feeding chamber is eliminated The Regumat Attack Oventrop device keeps the constant tempe...
Page 44: ...her precisely defined places STN EN ISO 12100 2 2004 Safety of machines General principles of construction of machines Part 2 Technical principles STN EN 953 A1 Safety of machines protection covers ST...
Page 45: ...pos 1 into the bottom chamber with cut part rearwards It is necessary to insert it horizontally and to turn it afterwards Insert the front part of the ashtray pos 3 in the same way Press the both part...
Page 46: ...emperature of 80 C after 1 3 loadings After the fuel burns out the heat is taken from the accumulation tank from the three way valve The time of outtake depends on the size of the tank and on the exte...
Page 47: ...uction m TION AGAINST OVERHEATING the norm EN 303 5 the inst the boiler overheating other purposes than boiler eating nlet into the cooling loop nd the cooling loop of the the functional cold water d...
Page 48: ...Insufficiently cleaned boiler Clogged air inlet into the combustion chamber Refill Set the flow and switching Matter of the project Burn dry and chopped wood Fix New chimney suitable connection Insta...
Page 49: ...perature in the boiler C Cause The temperature in the boiler is 95 C because of too big amount of fuel power shortage error by heat outtake or in the circuit pump Indicator light 3 red Shines Solution...
Page 50: ...ed Solution Reset Emergency program Actions of the regulator Flickers Load less fuel or remove the fault Automatically by the boiler temperature of 89 C NO Boiler temperature 90 C flue gas fan stop V1...
Page 51: ...the amount of the alternative air V1 V2 The boiler must be stopped manually and the button Not to shorten the service life of the boiler it is necessary to remove the fault immediately The guarantee c...
Page 52: ...me elapses Safety test Takes max 30 min and it is automatically terminated or interrupted if the boiler temperature is 110 C or the button has not been pressed for 30 seconds Operating range of the au...
Page 53: ...2 1 2 1 1 SL HN SN HL 4 4 1 T 95 1 ST C ST 2 PE PT 1 PT C PE BT 1 BT C PE 1 1 T 95 1 1 4 2 3 0 V 5 0 H z 1 TC 95 C KO 2 5 1 4 4 4 5 ATTACK DPX STANDARD t C t C t C KEY HV Main switch ST Flue gas therm...
Page 54: ...rature sensor STBS sensor of emergency thermostat HP circuit pump AP additional pump AS additional sensor RT room thermostat FS flue gas temperature sensor FAN ventilator STB emergency thermostat 1 bl...
Page 55: ...the bottom part of the regulator FUSE STB SENSOR MAINS 230 V 50 Hz PROTECTION CONDUCTOR BOILER SWITCHING CONTACT WITHOUT POTENTIAL SUCTION FAN CIRCUIT PUMP REGULATION OF AIR SECONDARY PRIMARY BOILER T...
Page 56: ...00 C R 138 5 T 200 C R 175 8 Fix the flue gas sensor into the flue connection by the bayonet flange Do not extend the connection conductors of the sensors Treat the boiler sensor and the safety thermo...
Page 57: ...mally open contact relay RK Normally closed contact relay L1 Phase PE Grounding N Zero wire Mains circuit breaker max 10 A Three wire flexi cable 1 5 mm2 Caution The covering of the boiler must be ear...
Page 58: ...DPX 30 PROFI ATTACK X 35 STANDARD ATTACK DPX 35 PROFI ATTACK X 40 STANDARD ATTACK DPX 40 PROFI ATTACK X 45 STANDARD ATTACK DPX 45 PROFI ATTACK combustion The boilers are intended to be a heat s const...
Page 59: ...onafterthe3rdyearofoperation Stamp signature of the service organization Date Stamp signature of the service organization Date Data of the customer legibly Name and surname Street ZIP code town Tel Bo...
Page 60: ...upozornenia ATTACK s r o producer reserves the right to change technical parameters and dimensions of boilers without previous warning Der Hersteller ATTACK s r o beh lt sich das Recht der technischen...