FUNCTIONS

1.  PULSE COUNT functions to trigger the unit based on desired number of pulse.

1) Select number of pulse, either 1 or 2, using Dip switch 1.
2) The unit will be triggered when pulse count within 10 seconds reaches the specified number.  Count will be reset 10 seconds

after the last pulse.

Usually 1 - 3 pulses are counted when human body crosses a field of view.   However, there may be a case where
only one pulse is counted when temperature difference between human body and stable background is small.
Please take this into your consideration for appropriate setup.

2.  ALARM MEMORY functions to identify the triggered detector(s) when two or more units are connected in one loop.

1)  Appropriate wiring with Memory terminal is required.
2)  Alarm output will be memorized when both terminals are disconnected.
3)  LED will light to indicate the memory while both terminals are connected.
4)  Memory will be reset and the LED will be turned off when power is cut off or both terminals are disconnected.

3.  SELF-DIAGNOSTIC CIRCUIT functions to detect malfunction of the unit itself.
1)  This will function anytime regardless of setup and condition of the unit.
2)  LED will flicker to indicate malfunction with terminals or amplifier.
3)  Flickering LED and alarm output will continue until power is cut off.
4)  LED will flicker regardless of condition of the unit during 30 second warm-up.

7

INITIAL SETUP

All dip switches are ON when shipped from factory.

Switch 1: PULSE COUNT
ON  :The unit will be triggered with one pulse.
OFF:The unit will be triggered with two pulses within 10 seconds.

Switch 2: ALARM MEMORY
ON  :LED will light only when triggered.
OFF:LED will never light.
NOTE:Regardless of dip switch setup, LED will light or flicker in the following cases.

1

During 30 second warm-up

2

When alarm memory is indicated

3

When Self-Diagnostic Circuit functions

Dip switches

4

Summary of Contents for IR36E

Page 1: ...y must be cut off during installation Keep power between 9 18 VDC anytime Attention Avoid intense shock and vibration After installation and setup make sure of performance and appropriate coverage of...

Page 2: ...5 open when power is not supplied N C opens when the sensor unit is removed Contact Rating 30VDC 0 1A for Resistive Loads Please see 6 Functions for details 9 18 VDC Function Wire size 0 3mm2 or 0 65...

Page 3: ...se unit 2Mount the base unit on ceiling and connect the wire to the unit 3Perform initial setup Please see 7 Initial setup for details 4Determine coverage Please see 8 Determining Coverage for details...

Page 4: ...indicate the memory while both terminals are connected 4 Memory will be reset and the LED will be turned off when power is cut off or both terminals are disconnected 3 SELF DIAGNOSTIC CIRCUIT function...

Page 5: ...heir area numbers are indicated on the label of the base unit Each arrow is centered in each coverage of 120 degrees and its number stands for each one of three 3 areas The same numbers are also marke...

Page 6: ...other unit s Self Diagnostic circuit is activated 11 COVERAGE Side View The unit must be installed so that intruders will cross field of view Failure of this doing may end up mis alarm When the covera...

Page 7: ...tive Loads 0 5 0 5 1 6 6ft sec 0 3 2 0 m sec Over 2 7 F 1 5 C difference against stable background at 3 3ft 1m sec under Environmental condition of 95 F 35 C 16 8 vertically Ceiling Indoor Mounting he...

Page 8: ...movement of an intruder and activates an alarm control panel Being only a part of a complete system we can not take responsibility for any damages or other consequences resulting from an intrusion AT...

Reviews: