• closed loop
Reference
Description
(1)
Machine
(2)
Heat exchanger
(3)
Cooling tower
(4)
Make up water
(5)
Blowdown
(6)
Standard Atlas Copco specification
• the application:
• standard (max water temperature 65°C / 149°F at the outlet)
• Energy Recovery (water temperature up to 95°C / 203°F)
Water quality
A full instruction for handling cooling water data is available at Atlas Copco.
In case water is not in line with recommended values or if any doubt, please refer to Atlas Copco.
Technical specifications
Parameter
Unit
Single Pass
(65°C /
149°F)
Single Pass
(95°C /
203°F)
Recirculating
(65°C / 149°F)
Closed
System
(65°C /
149°F)
Closed
System
(95°C /
203°F)
1
pH
6.8 - 9.3
6.8 - 9.3
6.8 - 9.3
7.5 - 9.3
7.5 - 9.3
2
Conductivity
µS / cm < 1500
< 600
< 4000
< 1500
50 - 600
3
Total Dissolved
Solids
mg / L
TDS to be measured for calculating RSI.
4
Ca-hardness
ppm
CaCO
3
< 500
< 2
< 500
< 1000
< 50