Drawing reference
Description
(1)
Larger than maximum allowed installation length.
(2)
Less than or equal to maximum allowed installation length
(3)
Minimum 1 mm of free space
Do NOT:
• Paint the rubber bellows of the expansion joint since:
• Solvents can damage the rubber cover.
• The colored coating avoids decent visual inspection of the rubber condition.
• Weld, cut or grind without protecting the rubber bellows
• Expose the compensator to permanent radiation heat above 90 °C (194 °F)
4.4
Electric cable size, fuses and cable length
General
Local regulations remain applicable if they are stricter than the values proposed below.
The voltage drop must not exceed 10 % of the nominal voltage. It may be necessary to
use cables with a larger size than those stated to comply with this requirement.
CSA/UL compressors
• Cables calculated according to CEC C22.1/NFPA 70
• Multicore cables on perforated tray or ladder system.
• Use 90 °C (194 °F) cables (Type R90, RW90, T90)
• 2 sets of fuses to be placed in series in order to meet the SCCR rating of 65kA (before
model year 2014)
• Cables have to be recalculated if the fuses that are used are bigger than the fuses that are
proposed.
Abbreviation
Description
FLA
Full Load Ampacity
MCA
Minimum Circuit Ampacity
Icc
Rated conditional short circuit current
SCCR
Short Circuit Current Rating
460 V - 60 Hz CSA/UL
Compressors designed for a maximum ambient temperature of 104 °F (40 °C) with IE2 motors
Type
Cables (90° cable) CEC
C22.1
Fuses RK5
(A)
Fuses LPJ
(A)
Maximum cable
length
(m)
ZR/ZT 110
2 x (3x MCM 250 + AWG
3)
2X (3X 175)
2X (3X 600)
193