380 V or 460 V supply
Install the transformer bridge on the primary winding side of the transformer,
installed in the electrical cubicle, as shown on the transformer (also shown here)
for the applicable supply voltage. Initially, the pumps have 400 V supply voltage
setting.
Pump control modes
Refer to
on page 43.
The control modes that follows can be selected:
▪
Local control: The pump accepts the command signals from the control panel.
It also accepts the start and stop command signals from the Clock function, if
programmed and set to on.
▪
Remote control: The pump accepts the command signals from the external
switches (remote control). It also accepts the command signals from the
emergency stop, start and stop command signals from the clock function.
▪
LAN control: The pump is controlled through a local network. Contact us.
Table 10 Wire assembly according to VDE 0295
Wire size (mm²)
Fine stranded wires VDE 0295 class
5
6
84 x 0.30
10
80 x 0.40
16
128 x 0.40
25
200 x 0.40
35
280 x 0.40
50
400 x 0.40