4.1 Connecting the hydraulic unit
to the heating circuit
4.1.1 Flushing the installation
Before connecting the hydraulic unit to the installation,
rinse out the heating system correctly
to eliminate
any particles that may affect the appliance's correct
operation.
Do not use solvents or aromatic hydrocarbons (petrol,
paraffin, etc.).
In the case of an old installation, provide a sufficiently
large decanting pot with a drain on the return from the
boiler and at the lowest point in the system in order to
collect and remove any impurities.
Add an alkaline product and a dispersant to the water.
Flush the installation several times before proceeding
to the final filling.
4.1.2 Connections
The heating circulation pump is built into the hydraulic
unit.
Connect the central heating pipes to the hydraulic unit
correctly according to the direction of circulation.
The pipe between the hydraulic unit and the heat collector
must be at least one inch in diameter (26x34 mm).
Calculate the diameter of the pipes based on flow rates
and lengths of the hydraulic systems.
Tightening torque: 15 to 35 Nm.
Use union connectors to make it easier to remove the
hydraulic unit.
Try to use connection hoses to avoid transmitting noise
and vibrations to the building.
Connect the drains from the drain valve and the safety
valve to the main sewer system.
Verify that the expansion system is correctly connected.
Check the expansion vessel pressure (pre-inflated to 1
bar) and the safety valve is calibrated.
The flow rate of the installation must be at least equal to
the minimum value mentioned in the specifications table
(section
1.4, page 7
)
.
The installation of a regulator
(other than those included in our configurations) which
reduces or stops the flow through the hydraulic unit is
prohibited.
4 Hydraulic connections
Installation and Operating Manual "1873- EN"
Alféa Extensa Duo A.I. Heat Pump
- 30 -
Summary of Contents for 024124
Page 17: ... Installation and Operating Manual 1873 EN 17 Alféa Extensa Duo A I Heat Pump ...
Page 29: ... Installation and Operating Manual 1873 EN 29 Alféa Extensa Duo A I Heat Pump ...
Page 81: ... Installation and Operating Manual 1873 EN 81 Alféa Extensa Duo A I Heat Pump ...
Page 86: ... Installation and Operating Manual 1873 EN Alféa Extensa Duo A I Heat Pump 86 ...
Page 87: ... Installation and Operating Manual 1873 EN 87 Alféa Extensa Duo A I Heat Pump ...