3.3 Checks and connection
"
The refrigeration circuit is very sensitive
to dust and humidity: check that the area
around the connection is clean and dry
before removing the plugs protecting the
refrigeration connectors.
"
Indicated blowing value: 6 bar for minimum
30 seconds for connection of 20 m.
Checking the gas connection (large diameter).
Connect the gas connection to the outdoor unit.
Blow dry nitrogen into the gas connection and inspect
its end:
-If water or impurities emerge, use a brand new
refrigeration connection.
Otherwise, proceed with flaring and connect the
refrigeration connection to the outdoor unit immediately.
Checking the liquid connection (small diameter).
Connect the liquid connection to the hydraulic unit.
Blow nitrogen into the
gas-condenser-liquid connection
system and inspect its end (outdoor unit side).
-If water or impurities emerge, use a brand new
refrigeration connection.
-
Otherwise, proceed with flaring and connect the
refrigeration connection to the outdoor unit immediately.
"
Take particular care to position the tube opposite
its connector so as not to risk damaging the
threads. A properly aligned connector can be
attached easily by hand without much force
being required.
-Where necessary, connect an adapter (reducer)
1/4''- 3/8'' or 1/2''- 5/8'' (see
figure 19
).
-Remove the plugs from the pipes and the refrigeration
connections.
-Comply with the indicated tightening torques.
figure 20 -
Tightening torques
Designation
Tightening torque
Flare 6.35 mm (1/4")
14 to 18 Nm
Flared nut 9.52 mm (3/8")
33 to 42 Nm
Flared nut 12.7 mm (1/2")
50 to 62 Nm
Flared nut 15.88 mm (5/8")
63 to 77 Nm
Plug (A) 3/8", 1/4"
20 to 25 Nm
Plug (A) 1/2"
25 to 30 Nm
Plug (A) 5/8"
30 to 35 Nm
Plug (B) 3/8", 5/8"
10 to 12 Nm
Plug (B) 1/2", 1/4"
12.5 to 16 Nm
Plug (A) and (B) : see
figure 22, page 25
.
Holding spanner
Torque wrench
figure 21 -
Checking refrigeration connections
Nitrogen
Nitrogen
Nitrogen
Gas
connection
Gas
connection
Gas
Liquid
connection
Installation and Operating Manual "1873- EN"
- 23 -
Alféa Extensa Duo A.I. Heat Pump
Summary of Contents for 024124
Page 17: ... Installation and Operating Manual 1873 EN 17 Alféa Extensa Duo A I Heat Pump ...
Page 29: ... Installation and Operating Manual 1873 EN 29 Alféa Extensa Duo A I Heat Pump ...
Page 81: ... Installation and Operating Manual 1873 EN 81 Alféa Extensa Duo A I Heat Pump ...
Page 86: ... Installation and Operating Manual 1873 EN Alféa Extensa Duo A I Heat Pump 86 ...
Page 87: ... Installation and Operating Manual 1873 EN 87 Alféa Extensa Duo A I Heat Pump ...