GSCM-mini-P                                                      Automatic Starting for Battery Charging 

 
The GSCM-mini-P can monitor either the generator battery voltage or a battery bank voltage and automatically start/stop the 
generator based on battery voltage.  This is accomplished by connecting the battery voltage to the battery sense input (terminal 
4).  The GSCM-mini 60Hz monitors a battery voltage range of 0 to 60VDC and automatically determines the start and stop set 
point based on battery voltage (12, 24, or 48VDC).  Below 16VDC - uses 12V thresholds, between 16 to 32V -uses 24V thresholds, 
above 32V - uses 48V thresholds.  This mode is disabled if the voltage on terminal 4 is less than 6V, (no connection). 
 

1.

 

The GSCM-mini-P monitors the battery sense input and when the battery voltage drops below the start threshold the 
Start  LED  begins  blinking  every  second.    When  the  battery  voltage  has  remained  below  the  start  threshold  for  5 
continuous minutes the auto start sequence begins.  If the battery voltage rises above the start threshold during the 5 
minute period the 5 minute timing cycle starts over. (Temporary battery voltage fluctuations such as instantaneous 
inverter  loads  will  not  start  the  GSCM).    The  start  LED  blinks  every  3  seconds  while  the  GSCM-mini  is  running  the 
generator in auto-start mode. 

2.

 

The GSCM-mini-P starts the generator as described in each of the three generator type sections. 

3.

 

The GSCM-mini-P shuts down the generator (as described in Sections 1, 2, or 3) whenever the battery voltage exceeds 
the stop threshold for 10 minutes.  The Start LED blinks (every second) during this 10 minute period.  The GSCM-mini 
will exit the 10 minute period and shutdown the generator if the battery voltage exceeds the stop threshold by +1.0V 
for a 12V system, 2V for 24V system and 4V for a 48V system.  The generator remains off until the battery voltage drops 
below the start threshold voltage. 

4.

 

The GSCM-mini-P will shut down the generator when it has run in auto-start battery charging mode for 6 hours and has 
not charge the battery above the shutdown threshold.  The GSCM-mini-P then returns to ready mode looking for a start 
command.  If the battery voltage drops below the Auto start threshold within 30 minutes of a max run time shut down 
the GSCM-mini-P will enter a max run time fault condition and lock out the start sequence and requires a power down 
reset.  The generator Hz LED will blink 3 quick blinks every 5 seconds and the fault LED is on continuously. 

5.

 

If the user wishes to manual-start the generator from a separate pressure switch, level switch, thermostat or inverter 
start contact, etc., the battery voltage is fed through the switch (pressure switch etc.) contact to Manual start terminal 
5. Closing the contact will cause the GSCM-mini to start the generator.  Some inverters provide a switch 12VDC signal 
to  start  the  generator.  This  switched  voltage  can  be  connected  directly  to  the  manual  start  terminal  5  and  ground 
terminal 7.  

 

GSCM-mini-P                                                                   Generator Emergency Shutdown 

 

The  GSCM-mini-P  Generator  Start  Stop  module  is  NOT  AN  EMERGENCY  SHUTDOWN  DEVICE!    If  the  manual  start  signal  is 
removed the generator will go through a normal shutdown which may take up to 15 seconds to completely shut down the 
generator. 
 
A  RECOMMENDED  EMERGENCY  SHUTDOWN  SOLUTION  is  to  install  a  separate  “Kill”  switch  and  label  it  as  such.  The 
recommended wiring is shown on page-2 of these instructions and also in Application 1. Disconnecting the power to the GSCM-
mini module will force the relays to open.  This will shut down generators that require a maintained run signal from K1 relay.  
However this also prevents the K2 relay from closing to shut down those generators requiring a momentary stop signal.  Using 
a double pole “Kill” switch and wiring the second pole in parallel with the K2 relay terminals will force the generator to stop in 
an emergency situation such as a fuel spill.  (See note 1 on wiring diagram, page 2, for Ignition/crank emergency shutdown 
option). 
 
 

Summary of Contents for GSCM-mini-P

Page 1: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 1 Revised 02 21 Generator Start Control Module Part GSCM mini P ATKINSON ELECTRONICS INC 14 West Vine Street Murray Utah 84107...

Page 2: ...pion Cummins Onan Duramax and Westinghouse Fixed start stop pulse times accounts for multiple start attempts by generator s ECU Maximum auto start run time limit 6 hours Remote run and fault indicatio...

Page 3: ...on description If adjustability is required then refer to the GSCM full function control module LED Indication Description The GSCM mini P has six indication LEDs The Start LED blinks every 5 seconds...

Page 4: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 4 Revised 02 21 GSCM mini P Wiring Diagram...

Page 5: ...ers the maximum crank lockout fault condition This lockout condition remains until the GSCM mini is reset by removing power from terminal 2 waiting 5 seconds and then reconnecting power see GSCM mini...

Page 6: ...expires and the GSCM mini runs thru its re start routine de energizing the K2 relay powering down the generator which clears it failed to start fault then waits 15 seconds and repeats the starting rou...

Page 7: ...the GSCM mini P receives the feedback signal it drops in to the run mode turning on the green run LED 5 If the generator fails to start after 6 starting attempts the GSCM mini P turns on its red faul...

Page 8: ...links during this 10 second period 3 Low frequency under Hz condition If the generator AC output is connected to terminals 9 and 10 and the generator Hz enable terminal 8 is grounded the GSCM mini mon...

Page 9: ...elow the start threshold voltage 4 The GSCM mini P will shut down the generator when it has run in auto start battery charging mode for 6 hours and has not charge the battery above the shutdown thresh...

Page 10: ...n and requires a reset K1 K2 Continuous status of K1 and K2 relays on Specifications Size 5 13 L x 2 853 W x 1 35 H Weight 20oz Mounting 2 screws through tabs Power 12VDC Battery 9 5 to 15VDC Quiescen...

Page 11: ...GSCM mini_p monitors the AC output to know when the generator has started The Champion ECU provides up to six starting attempts before going into a fault condition The GSCM mini P s terminal 6 is not...

Page 12: ...and common 30 tabs wires in series with the ground wire that connects to terminal 5 of the engine switch when not energized it grounds the ignition coil Engine switch to be left in the OFF position Th...

Page 13: ...ground terminal 85 connects to engine switch terminal 1 and terminal 87a connects to engine switch 5 Engine switch to be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal...

Page 14: ...grounds the ignition coil Engine switch to be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal 3 12vdc and to Samlex s normally open relay contact and the common contact...

Page 15: ...o be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal 3 12vdc and Outback s switched 12vdc maintained start run signal is wired to the GSCM mini P s manual start input Ou...

Page 16: ...nd stop the generator without an additional control relay A battery tender charger is used to keep the battery from discharging due to the engine switch being left on 24 7 The GSCM mini P s terminal 6...

Page 17: ...power switch and the starter motor The relay contact common 30 connects to the ECU s white wire that connects to the switch The generators power switch should remain in the OFF position The GSCM mini...

Page 18: ...from the date of shipment by Atkinson Electronics Inc or its authorized distributors to the original Customer Atkinson Electronics Inc will repair or replace at our option any defective products prov...

Reviews: