Atkinson Electronics GSCM-mini-P Manual Download Page 6

www.atkinsonelectronics.com

 

 

 

                                                    

Circuit Board Division 
800.261.3602 

Revised 02/21

 

GSCM-mini-P Option #2                  Cummins/Onan, Westinghouse push to start/stop 

 

The GSCM-mini-P’s configuration terminal # 6 is connected to +12VDC (terminal # 3), this configures the GSCM-mini-P  
for a 1 second start/stop pulse on the K1 relay contact and a maintained power/run on the K2 contact.  When the 
GSCM-mini-P is powered by connecting B+ (12.0 VDC) to terminal 2,  the Start LED turns on for 5 seconds while the 
GSCM-mini initializes with option #2 configuration then begins blinking the start LED once every 5 seconds.  The GSCM-
mini’s starting sequence is as follows. 

 

1.

 

The start LED blinks once every 5 seconds to indicate that the GSCM-mini is in a “ready” mode.  When a manual 
start signal is received, the start LED lights continuously.  After a 2 second delay, K2 relay energizes closing its 
normally open contact to power the generator’s ECU, then after another 2 second delay, it provides a 1 second 
start pulse by energizing the K1 relay contact for 1 second. The generator’s ECU then makes three attempts to 
start the generator.   

2.

 

If the generator fails to start during the three starting attempts and rest periods, approximately 50 seconds, the 
generator  will  go  into  a  failed  to  start  fault  requiring  the  generators  ECU  to  be  reset  by  powering  down  the 
generator.  The GSCM-mini-P starts a 1 minute timer when it provides the start pulse and looks for a valid run 
feedback signal.  

3.

 

The run feedback signal can be either: a 12vdc status pilot lamp signal provide by the generator that is connected 
to the GSCM-mini-P’s terminal #8, or by the generator producing its 120VAC output which would be connected to 
the GSCM-mini-P’s GenHz input (terminal #9 and 10).   

4.

 

When the generator starts and the GSCM-mini-P receives the feedback signal it drops in to the run mode turning 
on the green run LED. 

5.

 

If the generator fails to start after 3 three starting attempts, the GSCM-mini-P’s 1 minute start timer expires and 
the  GSCM-mini  runs thru  its  re-start  routine,  de-energizing  the  K2  relay  powering  down  the  generator, which 
clears it failed to start fault, then waits 15 seconds and repeats the starting routine.  

6.

 

If the generator fails to start after the second round of three attempts the GSCM-mini-P turns on its red fault LED 
and the GSCM-mini enters the Maximum crank lockout condition and the Generator Hz LED does a double blink. 
This lockout condition remains until the GSCM-mini is reset by removing power from terminal 2, waiting 5 seconds 
and reconnecting power.  This clears the lockout condition, and returns to ready mode. 

7.

 

If the generator starts but shuts down after a few seconds due to a fuel problem, etc.  The GSCM-mini goes thru 
its shutdown routine then re-enters ready mode after a 60 second delay.  During this delay the start LED will blink 
rapidly.  The GSCM-mini will then try to start the generator again in manual mode or after a 5 minute delay period 
in auto-start mode. 

8.

 

When  a  run  condition  is  detected,  the  GSCM-mini  turns  on  the  run  LED  and  open  collector  transistor  output 
(remote run lamp) and after a 60 second generator stabilization period it monitors the run feedback signal. 

9.

 

If the generator starts but shuts down after the 60 seconds stabilization period, due to a fuel problem, low oil 
pressure, broken AC Hz or 12V run pilot light status wire, the GSCM-mini turns off the run LED and turns off K2 
relay, and turns on the fault LED blinks the orange GenHz LED five times every two seconds.  The GSCM-mini enters 
a fault shutdown lockout condition and must be powered down to reset the fault lockout. 

10.

 

If no faults occur, the generator continues running until one of the following occurs:  The manual start signal is no 
longer received, the auto battery charge voltage or max run time has been reached while running in auto charge 
mode, an over or under Hz condition occurs if generator Hz shutdown is enabled or the generator runs out of gas. 

11.

 

Shutdown routine, K1 provide a 1 second stop pulse, then 15 second later K2 relay de-energizes, powering down 
the generator. 

12.

 

The generator remains off until another start signal is received. 

Summary of Contents for GSCM-mini-P

Page 1: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 1 Revised 02 21 Generator Start Control Module Part GSCM mini P ATKINSON ELECTRONICS INC 14 West Vine Street Murray Utah 84107...

Page 2: ...pion Cummins Onan Duramax and Westinghouse Fixed start stop pulse times accounts for multiple start attempts by generator s ECU Maximum auto start run time limit 6 hours Remote run and fault indicatio...

Page 3: ...on description If adjustability is required then refer to the GSCM full function control module LED Indication Description The GSCM mini P has six indication LEDs The Start LED blinks every 5 seconds...

Page 4: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 4 Revised 02 21 GSCM mini P Wiring Diagram...

Page 5: ...ers the maximum crank lockout fault condition This lockout condition remains until the GSCM mini is reset by removing power from terminal 2 waiting 5 seconds and then reconnecting power see GSCM mini...

Page 6: ...expires and the GSCM mini runs thru its re start routine de energizing the K2 relay powering down the generator which clears it failed to start fault then waits 15 seconds and repeats the starting rou...

Page 7: ...the GSCM mini P receives the feedback signal it drops in to the run mode turning on the green run LED 5 If the generator fails to start after 6 starting attempts the GSCM mini P turns on its red faul...

Page 8: ...links during this 10 second period 3 Low frequency under Hz condition If the generator AC output is connected to terminals 9 and 10 and the generator Hz enable terminal 8 is grounded the GSCM mini mon...

Page 9: ...elow the start threshold voltage 4 The GSCM mini P will shut down the generator when it has run in auto start battery charging mode for 6 hours and has not charge the battery above the shutdown thresh...

Page 10: ...n and requires a reset K1 K2 Continuous status of K1 and K2 relays on Specifications Size 5 13 L x 2 853 W x 1 35 H Weight 20oz Mounting 2 screws through tabs Power 12VDC Battery 9 5 to 15VDC Quiescen...

Page 11: ...GSCM mini_p monitors the AC output to know when the generator has started The Champion ECU provides up to six starting attempts before going into a fault condition The GSCM mini P s terminal 6 is not...

Page 12: ...and common 30 tabs wires in series with the ground wire that connects to terminal 5 of the engine switch when not energized it grounds the ignition coil Engine switch to be left in the OFF position Th...

Page 13: ...ground terminal 85 connects to engine switch terminal 1 and terminal 87a connects to engine switch 5 Engine switch to be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal...

Page 14: ...grounds the ignition coil Engine switch to be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal 3 12vdc and to Samlex s normally open relay contact and the common contact...

Page 15: ...o be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal 3 12vdc and Outback s switched 12vdc maintained start run signal is wired to the GSCM mini P s manual start input Ou...

Page 16: ...nd stop the generator without an additional control relay A battery tender charger is used to keep the battery from discharging due to the engine switch being left on 24 7 The GSCM mini P s terminal 6...

Page 17: ...power switch and the starter motor The relay contact common 30 connects to the ECU s white wire that connects to the switch The generators power switch should remain in the OFF position The GSCM mini...

Page 18: ...from the date of shipment by Atkinson Electronics Inc or its authorized distributors to the original Customer Atkinson Electronics Inc will repair or replace at our option any defective products prov...

Reviews: