Atkinson Electronics GSCM-mini-P Manual Download Page 10

www.atkinsonelectronics.com

 

 

 

                                                    

Circuit Board Division 
800.261.3602 

10 

Revised 02/21

 

LED Description and Meanings 

 

Start: 

One blink every 5 seconds = ready mode, looking for a start signal 

 

One blink every 2.5 seconds = auto start mode operation 

 

One blink every other second= auto start/stop period 

 

Continuous = manual start signal received 

 

Fast blink = 60 second delay after start signal removed before generator started 

 

Generator Hz Shutdown 

Fast blink = over speed condition 

 

Slow blink = under speed condition 

 

Double blink = maximum crank attempts reached, failed to start 
Triple blink = auto start attempted with-in 30 minutes of a max run time (6 hour ) shutdown 

 

Four blinks every 2 seconds = AC Hz or 12V run status signal lost during run mode 

 

Continuous = start function disabled, AC Hz detected while in ready mode 

 

Run 

Continuous = GSCM-mini has a valid run signal from generator 

 

Fault 

Continuous = GSCM-mini is in a fault condition and requires a reset 

 

K1 & K2 

Continuous = status of K1 and K2 relays on 

Specifications 

 
Size:  

5.13" L x 2.853" W x 1.35" H 

 
Weight: 

20oz. 

 
Mounting:  

2 screws through tabs 

 
Power:  

12VDC Battery  

 

9.5 to 15VDC 

 

Quiescent current < 10mA 

 

Relay current < 25mA each 

 
Manual Input:  

B+ (12VDC) input = on condition 

 

Open input = off condition 

 
Battery Input:  

0-60VDC 

 
Auto Start/ 
 
Stop Threshold:  

12V System 11.5V, 13.8V 

 

24V System 23.0V, 27.6V 

 

48V System 46.0V, 55.2V 

 
Relay  
Configuration:  

Open input = momentary crank 

(Terminal 6)  

Grounded input = maintained crank 

 

B+ (12VDC) input = ignition & crank 

 
Ambient Temp:          -40 to 85°C 
 
 

Gen. Hz Enable:         Open input =  
(Terminal 8) 

Generator Hz shutdown not active 

 

 

 

Grounded input =  

 

Generator Hz shutdown active 

 

 

12VDC input =  

 

Generator run Status input 

 

 

Over/under Hz shutdown 

 

not active 

 
Frequency Input:  

24VAC, 120VAC & 240VAC 0-100 Hz 

(Terminals 9 & 10) 
 

    Output Ratings:  

Two 10 AMP 28VDC relay contacts, 
K1 has   38VDC MOV across contact.   

 

  Two open collector NPN transistors,  

 

    maxium 300mA each 

 
Fault Detection:         Start failure, (3 attempts) 
 

    Over Hz condition (10 seconds) 

 

    Under Hz condition (10 seconds) 

 

    Max run time (6 hours) 

 

  Loss of AC Hz or 12V run status signal 

 

 
 
 
 
 
 

Summary of Contents for GSCM-mini-P

Page 1: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 1 Revised 02 21 Generator Start Control Module Part GSCM mini P ATKINSON ELECTRONICS INC 14 West Vine Street Murray Utah 84107...

Page 2: ...pion Cummins Onan Duramax and Westinghouse Fixed start stop pulse times accounts for multiple start attempts by generator s ECU Maximum auto start run time limit 6 hours Remote run and fault indicatio...

Page 3: ...on description If adjustability is required then refer to the GSCM full function control module LED Indication Description The GSCM mini P has six indication LEDs The Start LED blinks every 5 seconds...

Page 4: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 4 Revised 02 21 GSCM mini P Wiring Diagram...

Page 5: ...ers the maximum crank lockout fault condition This lockout condition remains until the GSCM mini is reset by removing power from terminal 2 waiting 5 seconds and then reconnecting power see GSCM mini...

Page 6: ...expires and the GSCM mini runs thru its re start routine de energizing the K2 relay powering down the generator which clears it failed to start fault then waits 15 seconds and repeats the starting rou...

Page 7: ...the GSCM mini P receives the feedback signal it drops in to the run mode turning on the green run LED 5 If the generator fails to start after 6 starting attempts the GSCM mini P turns on its red faul...

Page 8: ...links during this 10 second period 3 Low frequency under Hz condition If the generator AC output is connected to terminals 9 and 10 and the generator Hz enable terminal 8 is grounded the GSCM mini mon...

Page 9: ...elow the start threshold voltage 4 The GSCM mini P will shut down the generator when it has run in auto start battery charging mode for 6 hours and has not charge the battery above the shutdown thresh...

Page 10: ...n and requires a reset K1 K2 Continuous status of K1 and K2 relays on Specifications Size 5 13 L x 2 853 W x 1 35 H Weight 20oz Mounting 2 screws through tabs Power 12VDC Battery 9 5 to 15VDC Quiescen...

Page 11: ...GSCM mini_p monitors the AC output to know when the generator has started The Champion ECU provides up to six starting attempts before going into a fault condition The GSCM mini P s terminal 6 is not...

Page 12: ...and common 30 tabs wires in series with the ground wire that connects to terminal 5 of the engine switch when not energized it grounds the ignition coil Engine switch to be left in the OFF position Th...

Page 13: ...ground terminal 85 connects to engine switch terminal 1 and terminal 87a connects to engine switch 5 Engine switch to be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal...

Page 14: ...grounds the ignition coil Engine switch to be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal 3 12vdc and to Samlex s normally open relay contact and the common contact...

Page 15: ...o be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal 3 12vdc and Outback s switched 12vdc maintained start run signal is wired to the GSCM mini P s manual start input Ou...

Page 16: ...nd stop the generator without an additional control relay A battery tender charger is used to keep the battery from discharging due to the engine switch being left on 24 7 The GSCM mini P s terminal 6...

Page 17: ...power switch and the starter motor The relay contact common 30 connects to the ECU s white wire that connects to the switch The generators power switch should remain in the OFF position The GSCM mini...

Page 18: ...from the date of shipment by Atkinson Electronics Inc or its authorized distributors to the original Customer Atkinson Electronics Inc will repair or replace at our option any defective products prov...

Reviews: