Three Modes of Relay Operation 

 
There are 3 program options based on the generator 
make for the GSCM-mini-P’s two relay contacts to be 

configured

:  Champion, Cummins/Onan & 

Westinghouse, and Duramax   

This is accomplished with an 

optional jumper on terminal 6. 

Option  #1  Champion’s  inverter  generator:

  

Terminal  6  has  no  connection.  The  GSCM-mini-P 
program  is  configured  for  a  1  second  pulse  (K1)  to 
wake up the generator’s ECU, and a second 1 second 
pulse (K1) to begin the generators start sequence. On 
shutdown, the K2 relay produces a 1 second pulse for 
the  ECU  to  stop  the  generator.    See  Section  1  for 
operation description.

 

Option  #2  Cummins/Onan  &  Westinghouse 
generators:

 

Terminal  6  connected  to  B+  (12VDC).      

The  GSCM-mini-P  program  configures  K2  for  main-
tained operation and K1 for 1 second start/stop pulse 
operation.  The  K2 contact  wires  in  parallel  with  the 
power switch and K1 wires in parallel with the push 
button  switch.  A  SPDT  relay  is  used  to  open  the  
connection between ground and the Ignition coil. See 
Section 2 for operation description. 

Option  #3  Duramax  generator:

   

Terminal  6  is 

connected  to  ground.    The  GSCM-mini-P  program  is 
similar to option #2, instead of 3 start attempts per 1 
second  start  pulse,  It  is  configured  for  Duramax’s 
single 1 to 5 second start pulse, if the generator fails 
to  start  during  the  5  second  start  pulse,  the  mini-P 
generates another start pulse, is will attempt up to 6 
times to start the generator before going into a fault. 
See section 3 for operation description. 

If adjustability is required then 
refer to the GSCM full function 

control module. 

 

 

 

LED Indication Description 

 

The GSCM-mini-P has six indication LEDs.   

The Start LED blinks every 5 seconds to indicate it is ready for 
a start signal.  The LED will blink every 2.5 seconds to indicate 
its  running  in  auto  start  mode.    On  continuously  indicates 
running in manual start mode.  

The Generator Hz LED blinks to indicate over/under Hz fault 
and start failure due to maximum crank attempted.  A slow 
blink  indicates  an  under  Hz  condition  while  a  fast  blink 
indicates an over Hz condition.  On continuously indicates AC 
present  in  a  non-run  condition.    A  double  blink  indicates  a 
start  failure condition.   Four blinks  indicates  generator shut 
down due to its own fault condition or lack of fuel.  

The Run LED, On continuously indicates a valid run signal 
from the generator.   

The Fault LED, On indicates a fault condition has occurred 
and GSCM-mini is in lockout and must be reset.   

The K1 and K2 LEDs indicate the relay status. 

Operational Thresholds 

 
GSCM-mini-P’ fixed operational thresholds:  

 

Start Pulse:   

 

 

 1 to 5 seconds 

AC Crank Disconnect:   

 45Hz 

DC Crank Disconnect   

 Voltage greater than 9VDC 

Under Speed Shutdown: 

 55Hz 

Over Speed Shutdown: 

 65Hz 

Max Auto Start Run time: 

6 Hours 

Manual Start Run Time: 

Indefinitely 

Auto Start/Stop Thresholds:  Start 

 Stop 

12V system 

    11.5V    13.8V     Standard 

 

  24V system 

   23.0V    27.6V     Auto selects 

 

  48V system 

    46.0V    55.2V     Auto selects 

Relay Configuration: 

       Open input = Momentary Crank 

(Terminal 6)   

            Grounded input = Maintained Crank 

 

 

 

 

            B+ (12VDC) input = Ignition & Crank 

Fault Detection:   

Start failure (Depends on option) 

 

Over Hz condition (10 seconds) 

 

Under Hz condition (10 seconds) 

 

Max run time auto restart within 30m 

 

Generator stops due to its own fault condition

 

 

Summary of Contents for GSCM-mini-P

Page 1: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 1 Revised 02 21 Generator Start Control Module Part GSCM mini P ATKINSON ELECTRONICS INC 14 West Vine Street Murray Utah 84107...

Page 2: ...pion Cummins Onan Duramax and Westinghouse Fixed start stop pulse times accounts for multiple start attempts by generator s ECU Maximum auto start run time limit 6 hours Remote run and fault indicatio...

Page 3: ...on description If adjustability is required then refer to the GSCM full function control module LED Indication Description The GSCM mini P has six indication LEDs The Start LED blinks every 5 seconds...

Page 4: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 4 Revised 02 21 GSCM mini P Wiring Diagram...

Page 5: ...ers the maximum crank lockout fault condition This lockout condition remains until the GSCM mini is reset by removing power from terminal 2 waiting 5 seconds and then reconnecting power see GSCM mini...

Page 6: ...expires and the GSCM mini runs thru its re start routine de energizing the K2 relay powering down the generator which clears it failed to start fault then waits 15 seconds and repeats the starting rou...

Page 7: ...the GSCM mini P receives the feedback signal it drops in to the run mode turning on the green run LED 5 If the generator fails to start after 6 starting attempts the GSCM mini P turns on its red faul...

Page 8: ...links during this 10 second period 3 Low frequency under Hz condition If the generator AC output is connected to terminals 9 and 10 and the generator Hz enable terminal 8 is grounded the GSCM mini mon...

Page 9: ...elow the start threshold voltage 4 The GSCM mini P will shut down the generator when it has run in auto start battery charging mode for 6 hours and has not charge the battery above the shutdown thresh...

Page 10: ...n and requires a reset K1 K2 Continuous status of K1 and K2 relays on Specifications Size 5 13 L x 2 853 W x 1 35 H Weight 20oz Mounting 2 screws through tabs Power 12VDC Battery 9 5 to 15VDC Quiescen...

Page 11: ...GSCM mini_p monitors the AC output to know when the generator has started The Champion ECU provides up to six starting attempts before going into a fault condition The GSCM mini P s terminal 6 is not...

Page 12: ...and common 30 tabs wires in series with the ground wire that connects to terminal 5 of the engine switch when not energized it grounds the ignition coil Engine switch to be left in the OFF position Th...

Page 13: ...ground terminal 85 connects to engine switch terminal 1 and terminal 87a connects to engine switch 5 Engine switch to be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal...

Page 14: ...grounds the ignition coil Engine switch to be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal 3 12vdc and to Samlex s normally open relay contact and the common contact...

Page 15: ...o be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal 3 12vdc and Outback s switched 12vdc maintained start run signal is wired to the GSCM mini P s manual start input Ou...

Page 16: ...nd stop the generator without an additional control relay A battery tender charger is used to keep the battery from discharging due to the engine switch being left on 24 7 The GSCM mini P s terminal 6...

Page 17: ...power switch and the starter motor The relay contact common 30 connects to the ECU s white wire that connects to the switch The generators power switch should remain in the OFF position The GSCM mini...

Page 18: ...from the date of shipment by Atkinson Electronics Inc or its authorized distributors to the original Customer Atkinson Electronics Inc will repair or replace at our option any defective products prov...

Reviews: