Three Modes of Relay Operation
There are 3 program options based on the generator
make for the GSCM-mini-P’s two relay contacts to be
configured
: Champion, Cummins/Onan &
Westinghouse, and Duramax
This is accomplished with an
optional jumper on terminal 6.
Option #1 Champion’s inverter generator:
Terminal 6 has no connection. The GSCM-mini-P
program is configured for a 1 second pulse (K1) to
wake up the generator’s ECU, and a second 1 second
pulse (K1) to begin the generators start sequence. On
shutdown, the K2 relay produces a 1 second pulse for
the ECU to stop the generator. See Section 1 for
operation description.
Option #2 Cummins/Onan & Westinghouse
generators:
Terminal 6 connected to B+ (12VDC).
The GSCM-mini-P program configures K2 for main-
tained operation and K1 for 1 second start/stop pulse
operation. The K2 contact wires in parallel with the
power switch and K1 wires in parallel with the push
button switch. A SPDT relay is used to open the
connection between ground and the Ignition coil. See
Section 2 for operation description.
Option #3 Duramax generator:
Terminal 6 is
connected to ground. The GSCM-mini-P program is
similar to option #2, instead of 3 start attempts per 1
second start pulse, It is configured for Duramax’s
single 1 to 5 second start pulse, if the generator fails
to start during the 5 second start pulse, the mini-P
generates another start pulse, is will attempt up to 6
times to start the generator before going into a fault.
See section 3 for operation description.
If adjustability is required then
refer to the GSCM full function
control module.
LED Indication Description
The GSCM-mini-P has six indication LEDs.
The Start LED blinks every 5 seconds to indicate it is ready for
a start signal. The LED will blink every 2.5 seconds to indicate
its running in auto start mode. On continuously indicates
running in manual start mode.
The Generator Hz LED blinks to indicate over/under Hz fault
and start failure due to maximum crank attempted. A slow
blink indicates an under Hz condition while a fast blink
indicates an over Hz condition. On continuously indicates AC
present in a non-run condition. A double blink indicates a
start failure condition. Four blinks indicates generator shut
down due to its own fault condition or lack of fuel.
The Run LED, On continuously indicates a valid run signal
from the generator.
The Fault LED, On indicates a fault condition has occurred
and GSCM-mini is in lockout and must be reset.
The K1 and K2 LEDs indicate the relay status.
Operational Thresholds
GSCM-mini-P’ fixed operational thresholds:
Start Pulse:
1 to 5 seconds
AC Crank Disconnect:
45Hz
DC Crank Disconnect
Voltage greater than 9VDC
Under Speed Shutdown:
55Hz
Over Speed Shutdown:
65Hz
Max Auto Start Run time:
6 Hours
Manual Start Run Time:
Indefinitely
Auto Start/Stop Thresholds: Start
Stop
12V system
11.5V 13.8V Standard
24V system
23.0V 27.6V Auto selects
48V system
46.0V 55.2V Auto selects
Relay Configuration:
Open input = Momentary Crank
(Terminal 6)
Grounded input = Maintained Crank
B+ (12VDC) input = Ignition & Crank
Fault Detection:
Start failure (Depends on option)
Over Hz condition (10 seconds)
Under Hz condition (10 seconds)
Max run time auto restart within 30m
Generator stops due to its own fault condition