Atkinson Electronics GSCM-mini-P Manual Download Page 2

www.atkinsonelectronics.com

 

 

 

                                                    

Circuit Board Division 
800.261.3602 

Revised 02/21

 

Table of Contents 

Modes of Relay Operations

......................................... 

3

 

LED Indication Description

 .......................................... 

3

 

Operational Thresholds

 ............................................... 

3

 

Typical Wiring Diagram

 

…….. ....................................... 

4

 

Option 1 Diagram

 ......................................................... 

5

 

Option 2 Diagram

 ......................................................... 

5

 

Option 3 Diagram

 ......................................................... 

5

 

Option 1 Starting Sequence

 ........................................ 

6

 

Option 2 Starting Sequence

 ........................................ 

7

 

Option 3 Starting Sequence

 ........................................ 

8

 

Manual Off Auto Switch Options

 ............................... 

Fault Shutdown Conditions

 ......................................... 

Automatic Starting for Battery Charging

................. 

10

 

Generator Emergency Shutdown

 ............................. 

10

 

LED Description and Meanings

 ................................. 

11

 

Specifications

 .............................................................. 

11

 

Remote RV Generator Start Drawing

 ................ 

12

 

Outback Inverter/Inverter Style Drawing

 ......... 

13

 

Outback Inverter/Honda EUxx00is Drawing

 .... 

14

 

Samlex America EVO Inverter Drawing

 ............. 

15

 

Limited Warranty

 ..................................................... 

16 

Solving your generators two to 
three wire start-stop problem. 

 

 

 

 

 

Not Included But……. 

Outback 48 Volt inverter 
systems require isolation relay 
A0365 
 

 

 

 

 

 

 
 

 

 

 

 

 

 

 

 

 

 

 

Features & Applications 

 

Inexpensive 2 wire to 3 wire start controller for 
electric push to start/stop  Duel fuel generators 

 

Optimized for use with Outback Invertors 

 

Supports four manufactures generator control:  
Champion, Cummins/Onan, Duramax and 
Westinghouse 

 

Fixed start/stop pulse times, accounts for 
multiple start attempts by generator’s ECU  

 

Maximum auto-start run time limit (6 hours) 

 

Remote run and fault indication included 

 

ABS epoxy sealed for harsh environment 
operation 

 

 

Description 

The GSCM-mini-P (Pulse) is a micro-processor based 
generator start-stop module, designed to auto start-
stop generators that need a 3 to 4 wire connection 
from a 2 wire 12 volt manual start command.  The 
GSCM-mini-P automatically goes into run mode 
when it either receives a remote start indication 
lamp signal (connected to terminal 8) or an AC Hz 
signal from the generator (AC connected to terminals 
9 & 10
).  Various LEDs are blinked or turned on to 
indicated the run or fault status of the GSCM-mini-P.  
Manually resetting the GSCM-mini-P by removing 
the power and removes any lockout that allows the 
generator to restart if called to do so. 

The GSCM-mini-P is powered by 12VDC from the 
generator battery and can monitor the battery 
voltage and start the generator to charge its own 
battery.  The GSCM-mini-P is a limited function 
controller that is part of the GSCM family.

  

 

All auto start battery voltage thresholds are 
fixed, if adjustability is required use the GSCM 
full function Generator Start Control Module.

 

Summary of Contents for GSCM-mini-P

Page 1: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 1 Revised 02 21 Generator Start Control Module Part GSCM mini P ATKINSON ELECTRONICS INC 14 West Vine Street Murray Utah 84107...

Page 2: ...pion Cummins Onan Duramax and Westinghouse Fixed start stop pulse times accounts for multiple start attempts by generator s ECU Maximum auto start run time limit 6 hours Remote run and fault indicatio...

Page 3: ...on description If adjustability is required then refer to the GSCM full function control module LED Indication Description The GSCM mini P has six indication LEDs The Start LED blinks every 5 seconds...

Page 4: ...www atkinsonelectronics com Circuit Board Division 800 261 3602 4 Revised 02 21 GSCM mini P Wiring Diagram...

Page 5: ...ers the maximum crank lockout fault condition This lockout condition remains until the GSCM mini is reset by removing power from terminal 2 waiting 5 seconds and then reconnecting power see GSCM mini...

Page 6: ...expires and the GSCM mini runs thru its re start routine de energizing the K2 relay powering down the generator which clears it failed to start fault then waits 15 seconds and repeats the starting rou...

Page 7: ...the GSCM mini P receives the feedback signal it drops in to the run mode turning on the green run LED 5 If the generator fails to start after 6 starting attempts the GSCM mini P turns on its red faul...

Page 8: ...links during this 10 second period 3 Low frequency under Hz condition If the generator AC output is connected to terminals 9 and 10 and the generator Hz enable terminal 8 is grounded the GSCM mini mon...

Page 9: ...elow the start threshold voltage 4 The GSCM mini P will shut down the generator when it has run in auto start battery charging mode for 6 hours and has not charge the battery above the shutdown thresh...

Page 10: ...n and requires a reset K1 K2 Continuous status of K1 and K2 relays on Specifications Size 5 13 L x 2 853 W x 1 35 H Weight 20oz Mounting 2 screws through tabs Power 12VDC Battery 9 5 to 15VDC Quiescen...

Page 11: ...GSCM mini_p monitors the AC output to know when the generator has started The Champion ECU provides up to six starting attempts before going into a fault condition The GSCM mini P s terminal 6 is not...

Page 12: ...and common 30 tabs wires in series with the ground wire that connects to terminal 5 of the engine switch when not energized it grounds the ignition coil Engine switch to be left in the OFF position Th...

Page 13: ...ground terminal 85 connects to engine switch terminal 1 and terminal 87a connects to engine switch 5 Engine switch to be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal...

Page 14: ...grounds the ignition coil Engine switch to be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal 3 12vdc and to Samlex s normally open relay contact and the common contact...

Page 15: ...o be left in the OFF position The GSCM mini P s terminal 6 is connected to terminal 3 12vdc and Outback s switched 12vdc maintained start run signal is wired to the GSCM mini P s manual start input Ou...

Page 16: ...nd stop the generator without an additional control relay A battery tender charger is used to keep the battery from discharging due to the engine switch being left on 24 7 The GSCM mini P s terminal 6...

Page 17: ...power switch and the starter motor The relay contact common 30 connects to the ECU s white wire that connects to the switch The generators power switch should remain in the OFF position The GSCM mini...

Page 18: ...from the date of shipment by Atkinson Electronics Inc or its authorized distributors to the original Customer Atkinson Electronics Inc will repair or replace at our option any defective products prov...