ATIM_ACW-TCR_UG_EN_V1.0
c.
Number of probes
Parameter code(Byte 1)
Parameter value (Byte 2)
0x17
0x00 = No probes enabled
0x01 = only physical probe is enabled
0x11 = both probes are enabled
Note
: The value 0x10 is not possible because the virtual probe requires value from physical probe.
d.
Threshold configuration
Parameter code(Byte 1)
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
0xD5 (temperature threshold
probe 1)
0xD6 (temperature threshold
probe 2)
0xD7 (humidity threshold probe
1)
0xD8 (humidity threshold probe
2)
Upper threshold value
Lower threshold value
Hysteresis
Length
High threshold value
field: temperature in hundredths of ° C triggering the high threshold (
Big Endian
encoding)
Low threshold value
field: temperature in hundredths of ° C triggering the low threshold (
Big Endian
encoding)
Hysteresis
field: margin of uncertainty for thresholds in hundredths of ° C (
Big Endian
encoding)
Duration
field: minimum waiting time before triggering the alert after threshold is exceeded