ATIM_ACW-TCR_UG_EN_V1.0
b.
Configuration du ACW-TCR
Emission period and samples in the frame
The transmission period (
1
) corresponds to the time interval between each sending of a measurement frame. This
period can be configured from 10 min to 255 h and its default value is 1 hour.
In addition, it is possible to configure the number of samples in a frame (
2
). Thus, several measurements will be carried
out before the sending of the frame which will contain all these measurements.
For example, with a period of 12 minutes and several samples of 4, a measurement will be made every 3 minutes and
the 4 samples will be sent in a single frame every 12 minutes.
Finally, it is possible to apply a redundancy of the data (
3
), which means that samples having been sent in the frame
n-1, n-2 or n-3 could be sent again in the frame n to the continuation of the new measurement samples (the most
recent sample first in the frame and the least recent last).
For example, for a history depth of 3, data from the last 2 frames will be sent, in addition to the new data, in the next
frame.
Keep alive frame period
A life frame can be sent periodically (
4
). This frame will contain the supply voltage of the product.
The value of this period can be configured from 1 hour to 1 month. By default, the value is set to 4 days.