ENG - Manual of installation, use and maintenance.
210-0352_libretto_WHC_ATI_eng.docx
23
Jan-19
22.
MENU PARAMETERS AND DESCRIPTION
MENU 01 - "INSTALLER" FOR THE USER AND INSTALLER
Index
Description
Default
Range
Unit of
measurement
01
Minimum percentage of circulator operation
19
[5-100]
%
02
Time-out for operation in the antilegionella mode
20
[0-240]
Minutes
03
"Antifreeze" function - NOT AVAILABLE
0
[0-2]
04
Maximum fan speed
5600
[500 - 7500]
rpm
05
Minimum fan speed
2840
[500 - 5000]
rpm
06
Ignition speed
4500
[500 - 7500]
rpm
07
Inter-ventilation speed
3500
[500 - 7500]
rpm
08
Post-ventilation speed
4500
[500 - 7500]
rpm
09
Post-ventilation time
15
[0-240]
Seconds
10
Post-circulation time
6
[0-240]
Seconds
11
Maximum percentage of circulator operation
100
[30-100]
%
12
Solar system configuration - NOT AVAILABLE
0
[0-1]
-
13
Solar system set-point - NOT AVAILABLE
85
[30-90]
° C
14
Solar circulator Type n. ° 1 - NOT AVAILABLE
1
[1-2]
-
15
Minimum percentage of solar pump operation n. ° 1 - NOT AVAILABLE
50
[30-100]
%
16
Delta-on temperature of solar pump n. ° 1 - NOT AVAILABLE
6
[1-20]
° C
17
Delta-off temperature of solar pump n. ° 1 - NOT AVAILABLE
4
[1-20]
° C
18
Delta-modulation of solar pump n. ° 1 - NOT AVAILABLE
0
[1-30]
° C
19
Increase of solar circulator n. ° 1 - NOT AVAILABLE
1
[1-20]
-
20
Step for solar pump n. ° 1 - NOT AVAILABLE
1
[1-10]
-
21
Temperature limit for solar probes on solar panel - NOT AVAILABLE
180
[10-250]
° C
22
Temperature limit for solar probes on storage - NOT AVAILABLE
95
[10-100]
° C
23
"Solar Antifreeze" function - NOT AVAILABLE
0
[0-1]
-
24
Reset parameters
0
[0-1]
-
25
Operation type
1
[1-2]
-
26
Gas type
1
[1-3]
-