7
WIRING
Voltage Inputs: Connect the positive voltage input to contact #20; the
negative input to contact #19.
Current Inputs: Connect the positive current input to contact #20; the
negative input to contact #19.
Figure 7. Process and Linear Input Wiring
The Series C power supply accepts 100 to 250 Vac and 100 to 250
Vdc line power without any switch settings or polarity considerations.
All connections should be made in accordance with the National
Electrical Code and local regulations, using only NEC Class 1 wiring
for all power terminals.
It is advisable, but not necessary, to fuse one leg of the incoming
power line, contact #9 or #10, with a 2AG, 0.5 amp rated fuse. It is
recommended that only instrument power is fused - not power to the
load.
Figure 8. Power Wiring Connection
DUAL ALARM
OUTPUTS
OPTION #T: DUAL ALARM OUTPUT, N.O.
This optional hardware module provides alarm drive outputs. LED indicators A1 and A2 are used to indicate
alarm conditions as configured in the Alarm Menu.
Option Description:
Option T Dual alarm, N.O.
Load Limits:
Max. Load Current
1 A rms
Min. Load Current
0.5 mA rms
Power Factor Range
0.2 to 1.0 (can drive small motors, solenoids, valves, and contactors)
Max. Surge Current
Non-repeating for 1 second
7.5 A
Max. I
2
T for fusing (0.01 sec)
4.5 amp-squared seconds (1 A - ABC1 typical fuse)
Figure 10. Wiring for Dual Alarm Outputs
WIRING FOR
OPTIONS
Load
Load
1 amp fuse
1 amp fuse
20-240 Vac
20-240 Vac