CONTROL MENU
The C Series controllers support both PID and on/off control. If the controller is equipped with
two standard outputs, the outputs can be configured for two different types of control. The
parameters used to customize the control operation are in the
(control) menu which is avail-
able only when the security access level is set to
(configuration) or
(factory).
If both outputs are configured for use with alarms or turned off (using the output 1 type and output 2 type
parameters), then the
(control) menu will not be displayed.
Display
Parameter
Available Selections
Output 1 Type
- PID control
o
f Output 1
- On/Off control of Output 1
- Output 1 set to OFF
- Alarm settings on Output 1
Output 2 Type
- PID control of Output 2
- On/Off control of Output 2
- Output 2 set to OFF
- Alarm settings on Output 2
Note:
the above table shows the options that first appear in the
OUTPUT
menu. Once the type of
control is selected, other options / selections are made available in the corresponding
CONTROL
menu. For the sake of clarity, these different selections are shown in the following examples of
PID CONTROL
options and
ON/OFF CONTROL.