www.atestgaz.pl
Figure 6: Closed loop configuration for sets of Alpa EcoWent XT and Alpa EcoDet XT detectors
Cross-section of
a single cable
conductor
[mm
2
]
A set of one Alpa EcoWent XT Gas Detector and one Alpa EcoDet XT Gas Detector
System without backup battery supply
(U
IN
= 24 V)
System with backup battery supply
(U
IN(min)
= 20 V)
L1 [m]
L2 [m]
Quantity of sets
L1 [m]
L2 [m]
Quantity of sets
0,75
53
426
13
44
355
11
88
430
12
78
358
10
126
437
11
162
411
9
169
449
10
217
435
8
218
467
9
-
-
-
1
59
494
15
71
413
12
94
498
14
108
419
11
131
504
13
149
429
10
172
514
12
197
446
9
217
528
11
252
490
8
1,5
40
599
19
66
501
15
75
603
18
101
505
14
108
605
17
139
512
13
144
610
16
181
523
12
184
619
15
228
539
11
227
631
14
-
-
-
2,5
24
834
28
38
698
23
55
835
27
70
700
22
87
837
26
103
703
21
120
840
25
137
707
20
154
844
24
173
713
19
Table 6: Maximum quantity of sets of Alpa EcoWent XT and Alpa EcoDet XT – closed loop configuration
Atest Gaz
A. M. Pachole sp. j.
ul. Spokojna 3, 44-109 Gliwice, Poland
VAT No.: PL 9691433231
tel.: +48 32 238 87 94
fax: +48 32 234 92 71
e-mail: [email protected]
p. 6/7
Appendix: PU-Z-098-ENG R06
•
Length L1 [m]
Detectors sets installed 30 m apart
Length L2 [m]
Summary of Contents for Alpa EcoWent XT