Eagle Eye Battery Room
Venting System 115V AC
Executive Summary
Eagle Eye's hydrogen gas detector and forced ventilation fan system designed for use in
battery charging rooms and other areas where Hydrogen may be present. The system
consists of a minimum of two parts, a hydrogen gas detector with relay contacts that
mounts in the highest part of the room and a large vent fan enclosure mounted through
the outside wall. The system is NFPA compliant. The system has four fans factory rated
at 850 CFM each. This conforms to N+ 1 for 2550 CFM. The vent is equipped with a
Positive Airflow Shut Off. These doors can be closed by an external electrical command.
They will stop any airflow from passing through the fans. Available power options are
110 V AC, 24 V DC, or minus 48 V direct current. It is fused at 10 amps for -48v. The
vents can be daisy chained, more than one vent can be controlled by one gas detector.
More than one hydrogen gas detector can activate a vent. The unit usually is set up to
exhaust air but can be factory configured to source forced air into a room. These units
are designed with flexibility in mind.