Features of the
Eagle Eye
Hydrogen Gas Detector
Should the concentration of hydrogen gas in the air surrounding the sensor reach 1% by
volume (10,000 ppm), the "1% Caution" yellow LED will light and the 1% internal relay
will close. Should the hydrogen gas concentration reach 2% by volume (20,000 ppm), the
"2% Warning" red LED will flash and an 80 db alarm will sound; the 1% relay will
remain closed and, if a Dual-Relay model, the 2% internal relay will close. Either relay
can activate a remote exhaust fan and/or alarm.
Dimensions:
Height 7 " (17.8 cm.)
Width 4-3/4 " (12.0 cm.)
Depth 2-1/2 " ( 5.5 cm.)
Mounting:
Four 3/16 " (4.5 mm.) screws
Power Requirements:
24, 48 volts dc. or 115 VAC as ordered
Relay(s):
At 2% SPDT.
At 1% SPDT
Operating Temperature:
14 to 104 degrees F ( -10 to 40 degrees C)