The damper- jack is affixed to the outside wall with normal fasteners by others.  It 
measures 24 inches square and needs an outside clearance of 30 inches. A one inch flange 
is provided to attach the unit and is in addition the listed dimensions. 

There are two different styles of wall jack available.  There is a standard wall jack, and an 
optional 90° wall jack where there is a high probability of heavy mechanical damage to 
the outside wall of the building. 

www.eepowersolutions.com | Tel: 1-877-805-3377 | Fax: 1-414-962-3660 | [email protected] | V1.0

Summary of Contents for VS-24

Page 1: ...This conforms to N 1 for 2550 CFM The vent is equipped with a Positive Airflow Shut Off These doors can be closed by an external electrical command They will stop any airflow from passing through the...

Page 2: ...1 4 2 3 1 2 4 2 3 2 2 and 4 2 3 3 All the active component parts on the Eagle Eye Fan Battery Room Exhaust Fan With Positive Airflow Shut Off System that are subject to testing are certified by the Un...

Page 3: ...sh and an 80 db alarm will sound the 1 relay will remain closed and if a Dual Relay model the 2 internal relay will close Either relay can activate a remote exhaust fan and or alarm Dimensions Height...

Page 4: ...d turn on the fans when the atmosphere reached 1 hydrogen It would sound the alarm at 2 hydrogen Both of these would have been well before the lean mixture of hydrogen could ignite During this period...

Page 5: ...and the Positive Airflow Shut Off closed This will prevent the air passage through the fan from acting as a chimney and drawing oxygen rich fresh air into the burning room After Positive airflow shut...

Page 6: ...ow these louvered dampers open and gravity will close them These louvered dampers do add a restriction to the airflow and will decrease the CFM somewhat Louver open Louver closed Installation The batt...

Page 7: ...provided to attach the unit and is in addition the listed dimensions There are two different styles of wall jack available There is a standard wall jack and an optional 90 wall jack where there is a h...

Page 8: ...spacer to provide room for louver movement The spacer louver and rain hood come from the factory as an assembly It is ready for installation The louver is the only installation difference Louver set u...

Page 9: ...plied by others After you are satisfied with the first hydrogen gas detector press the test button on each successive hydrogen gas detector in the loop It is also possible to activate the system by ex...

Page 10: ...on When you install the fan reset the doors by lifting them up and latching them in place Make sure the fan is powered up Close the positive shut down control contacts by pulling the Firefighter s Eme...

Reviews: