OM226142 rev C
41
It is mounted in a separate cabinet and it is equipped with free voltage contacts for the
indication of the switch position (open-closed) and fuses condition.
6.5.1 Connections
The battery switch with fuses is connected between the UPS and the external battery
cabinet as illustrated below.
Picture 32 – Connection of the battery fused switch
6.5.2 Technical data
-
Colour:
RAL
7032
-
Protection
degree:
IP20
UPS
(kVA)
20 30 40 60 80
L – mm
400
500
P – mm
200
200
H – mm
400
700
L1 – mm
360
460
H1 – mm
360
660
UPS
(kVA)
20 30 40 60
80
Switch type
2 pole fused switch
3 poles fuses
Fuses size (A)
80 Gg
80 Gg
125 Gg
160 Gg
400 Gg