OM226142 rev C
33
5.2.3.2
Dimensions and distances
Picture 23 – Dimensions and distances from the walls
UPS
(kVA) 20 30 40 60 80
L – mm
690
P – mm
865
H – mm
1345
X (min.) – mm
50
Y (min.) – mm
500
ADD. CABINET
AS028
AS029
L1 – mm
620
815
P1 – mm
645
820
H1 – mm
1150
1340
The additional cabinets AS028 and AS029 are cabinets for external battery.