Astria MMST43 Installation And Operation Instructions Manual Download Page 15

13

5)  After the last side walls are in place it is time to install the 

rebar. Mix approx. 2 cu. ft. of Ready-Mix Concrete. Insert 

the 36” rebar vertically through the cells, into the holes in 

the hearth, adjacent to the rebar and/or all-thread sticking 

up from the hearth. Fill all cells with Ready-Mix Concrete 

mix. 

 

 

Keep  damp  at  all 

times while applying 

mortar.

Figure 20

IMPORTANT! Keep in mind that, when applying the 

mortar, you must frequently run a damp sponge to the 

parts before mortar is applied!

6)  Set the lintel in place as shown in 

Figure 21

. Check that 

all is level. If you need to make adjustments, use  shims. 

Place one or more of these shims between the lowest 

wall component and the top surface of the base plate. 

Once you are satisfied with the degree of levelness, you 

can address any gap that may have occurred with an 

appropriate amount of mortar.

 

 

Note: 

Although you are cautioned to use mortar 

sparingly because it does have such holding power, you 

should look over the firebox assembly at the end and fill 

in any gaps, especially joint connections, with the mortar. 

Needless to say, you must make adjustments to be sure 

the fireplace is level and square while the mortar is still 

wet.

7)  Set the remaining lintel as shown in 

Figure 22

.

8)  Now you are ready to start the smoke dome assembly. 

Take the lower side dome positioned so that the beveled 

face lines up with the inward angles of the lintel sides 

(see 

Figure 23

). Top surfaces should be level.

9)  Now position the front/rear smoke dome parts on top of 

dome. These parts require care in leveling, noting the 

parts have a slight bevel. Check for vertical with level 

(

Figure 24

).

10) As you are connecting each Grand Meridian component, 

be certain you are following the instructions given 

previously for using mortar. Stop to look at the smoke 

dome side, front and rear walls to see that they are 

aligning correctly and that the surfaces be smooth and 

uniform. Make sure connections are covered with an 

adequate amount of mortar. Remember that you have 

the option of using shims and covering them with mortar 

if you need to. Make any adjustments to the fireplace 

alignment before continuing to the next step.

11)  Check your assembly here. If things are proceeding as 

they should be, the finished top surface should be flat 

and level.

12) Now you can set the smoke dome top plate into position. 

Be sure that it is flush in every direction as you place it 

on the crest of the smoke dome wall assembly.

Figure 21

Building 

Lower 

Firebox

Figure 22

Lintel Assembly

Lintel

Lintel

Figure 23

Lower Side 

Dome Assembly

Figure 24

Lower Dome 

Assembly

Summary of Contents for MMST43

Page 1: ...ns information that will enable you to obtain replacement parts or accessory items when needed Keep it with your other important papers WARNING THIS FIREPLACE IS APPROVED FOR USE AS A WOOD BURNING FIR...

Page 2: ...This page has been left intentionally blank...

Page 3: ...EEN TESTED FOR USE ONLY WITH APPROVED GLASS DOORS TO REDUCE THE RISK OF FIRE OR INJURY CONSULT OWNER S MANUAL THIS FIREPLACE IS DESIGNED FOR USE ONLY WITH SOLID WOOD LOGS PLUMBED LPG OR NG LOG LIGHTER...

Page 4: ...2 MMST43 Fireplace Parts Diagrams Combustible Floor Systems Non Combustible Floor Systems 1 3A 3 6 7 8 10 9 14 13 17 16 18 19 12 Figure 1 20 Figure 2 1 3A 3 6 7 8 10 9 14 13 19 12 20...

Page 5: ...43STFRBL Running Bond ITEM P N DESCRIPTION QTY 1 MFPST 43 1 HEARTH Left or Right 2 3 MFPST 43 3 SIDE WALL 5 3A MFPST 43 3A SIDE WALL W 4 KNOCKOUT 1 6 MFPST 43 6 LINTEL 1 7 MFPST 43 7 DOME SIDE LOWER 2...

Page 6: ...ure 3 Overall Dimensions Non Combustible Floor Systems Figure 4 IF WOOD FRAMING IS UTILIZED IT MUST BE HELD 18 INCHES MIN FROM TOP OF LINTEL AND 2 INCHES MIN CLEARANCE MUST BE MAINTAINED ALL AROUND FI...

Page 7: ...OF OPENING 20 1 2 THICK CONCRETE BOARD 8 METAL PLATFORM 2 INCH CLEARANCE TO COMBUSTIBLES BOTH SIDES OF FIREPLACE If using a raised hearth or metal base plate note that a combustible wood header must b...

Page 8: ...ance manufacturer s literature regarding sizing and suitability for the installation into this Enclosure prior to installation Statement of Intended Use The Grand Meridian Fireplace is a modular refra...

Page 9: ...s Spacing and clearance as it relates to combustible materials Familiarity of installation for all components The strength of the floor on which it rests Chimney system measurements Choice of material...

Page 10: ...responsibility of the contractor installer not the manufacturer to ensure that adequate combustion air is provided for proper function of this fireplace Fireplaces take up a large volume of replacemen...

Page 11: ...ts Note that additional floor joists may be required to support the weight of the firebox and chimney Where the floor joists run parallel to the front of the firebox anchorage can be accomplished in l...

Page 12: ...rs having a moisture content of less than 16 per cent at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted for the deflection resul...

Page 13: ...ng an on site constructed hearth extension you may use a sand cement grout between the hearth and extension instead What You Will Need You will find that the Grand Meridian Fireplace is designed to be...

Page 14: ...Once you have inserted any shims you will want to cover any gaps that may have resulted with the mortar MMST43 Fireplace Assembly 1 Place the Grand Meridian Fireplace hearth base on top of your non c...

Page 15: ...7 Set the remaining lintel as shown in Figure 22 8 Now you are ready to start the smoke dome assembly Take the lower side dome positioned so that the beveled face lines up with the inward angles of th...

Page 16: ...hat where the Support Box is located Firestop Radiation Shields also provide complete separation from one floor space to another or attic space as required by most codes When the double wall pipe pass...

Page 17: ...dian Fireplaces they cannot take any liability or responsibility for they way the firebrick or the firebrick mortar performs It is not unusual in the course of the life of the firebrick or the firebri...

Page 18: ...p air to function properly and some local building codes may require outside combustion air to be provided If no make up air is provided improper flue drafting may occur creating negative pressure whe...

Page 19: ...the base of the Anchor Plate Apply ceramic blanket gasket to the gasket cement 2 Apply balance of gasket cement in a 1 4 one quarter inch bead on top of smoke dome top approx 3 3 inches outside of out...

Page 20: ...s of firewood at any given time Consider that this typical fuel load is three to four dry hardwood logs that are about 6 six inches to 8 eight inches in diameter 4 Without a grate for your firewood to...

Page 21: ...er seals that surround it If you find any cracks or openings around screws or nails seal them to avoid any roof or chimney chase leaks SURFACE CRACKS The Grand Meridian FIREPLACES are manufactured usi...

Page 22: ...ncrete slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MI...

Page 23: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Page 24: ...pect for any injury or damage to the building or structure in which the fireplace has been installed or to the persons or property therein arising out of the use misuse or installation of properly man...

Reviews: