Astria MMST43 Installation And Operation Instructions Manual Download Page 14

12

a)  Mixing  the  mortar  –  The  mortar  comes  premixed  and 

should be dry. Be sure to use clean water and work it up 

into a mixture that is pasty but not lumpy. If it’s too thin 

and the surfaces don’t stay moist, the components will not 

adhere. Load the mixture into a standard grout bag.

b)  Apply about ½” (one-half inch) thread of mortar. The mortar 

bead  should  be  approximately  ½”  (one-half  inch)  away 

from all edges. The mortar has a considerable amount of 

holding power so do not overload the components with too 

much mortar. Keep the components moist at all times!

c)  Some  mortar  will  “ooze  out”  when  placing  components 

together, this is normal. Wipe excess away with a trowel. Do 

not cover component surfaces completely with mortar. Do 

not apply the mortar in thick bands even if the component 

you are working with is larger than the rest. You will want 

to apply “stripes” of mortar in these situations.

d)  Make sure components are level. It’s extremely important 

that you pay careful attention to how you are assembling 

the Grand Meridian Fireplace since every component builds 

on the next. If you have to make any kind of an adjustment, 

do not try to do it “by loading an opening” with mortar, this 

will only result  in a fireplace that will not be plumb or level.

 

Use wood shims instead. 

You will find these small wood 

shims supplied with the Grand Meridian Fireplace

 and 

you can nudge them in between openings to achieve the 

precision  you  need  in  making  component  adjustments. 

Once  you  have  inserted  any  shims,  you  will  want  to 

cover any gaps that may have resulted with the mortar.

 

MMST43 Fireplace Assembly

1)  Place the Grand Meridian Fireplace hearth base on top 

of your non-combustible floor or metal base. For concrete 

slabs, supporting floor needs to be rated at ASTM 90. 

2)  a) 

Combustible Floor Installations: 

 

Mix up a batch of mortar and place hearth slabs on  

  top of cement board which sits on top of the Raised  

  Metal Platform (see Figure 15). All-thread rods should  

  stick up through the holes on the hearth slabs.

 

  

b) 

Non-combustible Floor Installations: 

 

Draw an outline of the hearth area based on the

 

  dimensions shown in Figure 18. Position Hearth slabs

 

  and mark rebar center locations (see Pg. 10, Fig.14).

 

  Drill 4 inches into concrete slab and secure the four

 

  pieces of rebar with epoxy.

3)  Before installing the side walls, confirm placement of 

outside combustion air side block (if required), this can 

be installed either side depending on which side is 

accessible to outside combustion air. Prepare side wall 

footprint with the prepared mortar. 

4)  Keep the assembly of the next sections of the firebox 

side walls moving up, keeping components moist, 

mixing mortar as you need it and threading the mortar 

appropriately as you stack each section, one onto the 

next. Constantly check for squareness and levelness 

while building each course of block. As you complete 

each section, make certain that you adhere the mortar at 

each and every joint.

Figure 18

Four 26ga.galv. 4” wide

Hearth Ember Shields 

required (not supplied)

LH Hearth 2nd

RH Hearth 1st

53”

28”

Apply mortar 

between joints

2” min 

overlap typ.

Figure 19

Setting Firebox Sides

Summary of Contents for MMST43

Page 1: ...ns information that will enable you to obtain replacement parts or accessory items when needed Keep it with your other important papers WARNING THIS FIREPLACE IS APPROVED FOR USE AS A WOOD BURNING FIR...

Page 2: ...This page has been left intentionally blank...

Page 3: ...EEN TESTED FOR USE ONLY WITH APPROVED GLASS DOORS TO REDUCE THE RISK OF FIRE OR INJURY CONSULT OWNER S MANUAL THIS FIREPLACE IS DESIGNED FOR USE ONLY WITH SOLID WOOD LOGS PLUMBED LPG OR NG LOG LIGHTER...

Page 4: ...2 MMST43 Fireplace Parts Diagrams Combustible Floor Systems Non Combustible Floor Systems 1 3A 3 6 7 8 10 9 14 13 17 16 18 19 12 Figure 1 20 Figure 2 1 3A 3 6 7 8 10 9 14 13 19 12 20...

Page 5: ...43STFRBL Running Bond ITEM P N DESCRIPTION QTY 1 MFPST 43 1 HEARTH Left or Right 2 3 MFPST 43 3 SIDE WALL 5 3A MFPST 43 3A SIDE WALL W 4 KNOCKOUT 1 6 MFPST 43 6 LINTEL 1 7 MFPST 43 7 DOME SIDE LOWER 2...

Page 6: ...ure 3 Overall Dimensions Non Combustible Floor Systems Figure 4 IF WOOD FRAMING IS UTILIZED IT MUST BE HELD 18 INCHES MIN FROM TOP OF LINTEL AND 2 INCHES MIN CLEARANCE MUST BE MAINTAINED ALL AROUND FI...

Page 7: ...OF OPENING 20 1 2 THICK CONCRETE BOARD 8 METAL PLATFORM 2 INCH CLEARANCE TO COMBUSTIBLES BOTH SIDES OF FIREPLACE If using a raised hearth or metal base plate note that a combustible wood header must b...

Page 8: ...ance manufacturer s literature regarding sizing and suitability for the installation into this Enclosure prior to installation Statement of Intended Use The Grand Meridian Fireplace is a modular refra...

Page 9: ...s Spacing and clearance as it relates to combustible materials Familiarity of installation for all components The strength of the floor on which it rests Chimney system measurements Choice of material...

Page 10: ...responsibility of the contractor installer not the manufacturer to ensure that adequate combustion air is provided for proper function of this fireplace Fireplaces take up a large volume of replacemen...

Page 11: ...ts Note that additional floor joists may be required to support the weight of the firebox and chimney Where the floor joists run parallel to the front of the firebox anchorage can be accomplished in l...

Page 12: ...rs having a moisture content of less than 16 per cent at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted for the deflection resul...

Page 13: ...ng an on site constructed hearth extension you may use a sand cement grout between the hearth and extension instead What You Will Need You will find that the Grand Meridian Fireplace is designed to be...

Page 14: ...Once you have inserted any shims you will want to cover any gaps that may have resulted with the mortar MMST43 Fireplace Assembly 1 Place the Grand Meridian Fireplace hearth base on top of your non c...

Page 15: ...7 Set the remaining lintel as shown in Figure 22 8 Now you are ready to start the smoke dome assembly Take the lower side dome positioned so that the beveled face lines up with the inward angles of th...

Page 16: ...hat where the Support Box is located Firestop Radiation Shields also provide complete separation from one floor space to another or attic space as required by most codes When the double wall pipe pass...

Page 17: ...dian Fireplaces they cannot take any liability or responsibility for they way the firebrick or the firebrick mortar performs It is not unusual in the course of the life of the firebrick or the firebri...

Page 18: ...p air to function properly and some local building codes may require outside combustion air to be provided If no make up air is provided improper flue drafting may occur creating negative pressure whe...

Page 19: ...the base of the Anchor Plate Apply ceramic blanket gasket to the gasket cement 2 Apply balance of gasket cement in a 1 4 one quarter inch bead on top of smoke dome top approx 3 3 inches outside of out...

Page 20: ...s of firewood at any given time Consider that this typical fuel load is three to four dry hardwood logs that are about 6 six inches to 8 eight inches in diameter 4 Without a grate for your firewood to...

Page 21: ...er seals that surround it If you find any cracks or openings around screws or nails seal them to avoid any roof or chimney chase leaks SURFACE CRACKS The Grand Meridian FIREPLACES are manufactured usi...

Page 22: ...ncrete slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MI...

Page 23: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Page 24: ...pect for any injury or damage to the building or structure in which the fireplace has been installed or to the persons or property therein arising out of the use misuse or installation of properly man...

Reviews: