Astria MMST43 Installation And Operation Instructions Manual Download Page 11

9

Supporting Floor Systems

It is the ultimate responsibility of the installer to ensure that 

proper concrete slab supports are used.

WARNING

 to the licensed design professional and/or building 

contractor: It is your responsibility to be certain that the Grand 

Meridian can be properly supported by the combustible floor 

system on which the fireplace will rest.

For fireplace support foundations installed on concrete refer to 

Appendix I and II (

pages 20 & 21 

) for specific instructions.

Rebar locations

  Lay-out the position of the fireplace and drill holes where 

the rebar will be located. Secure eight #3 rebar 4 inches into 

concrete foundation with ITW Epoxy or Simpson Epoxy.  

Follow manufacturer’s instructions for installation of rebar into 

slab.

Wood Floor

  Anchorage of fireplace to wood floor construction is required. 

Refer to 

Figure 10

 for anchorage locations. Four anchors are 

required to attach to the sub-flooring framing.

Crawl Space or Upper Floor:

  For installation of firebox over combustible crawl spaces or 

upper floors, anchorage of the firebox is required. Illustrations 

of  examples  of  possible  anchorage  methods  are  shown  in 

Figures 10 thru 13 depending upon the type of floor framing. 

Final  method  of  anchorage  to  be  determined  by  licensed 

design professional.

  For conventional framing where the floor joists are parallel 

with the sides of the firebox, the addition of floor joists to align 

with  the  anchor  brackets  allows  the  brackets  to  be  directly 

connected to the floor joists.

  Note that additional floor joists may be required to support 

the weight of the firebox and chimney. Where the floor joists 

run  parallel  to  the  front  of  the  firebox,  anchorage  can  be 

accomplished  in  like  manner  as  shown  in  Figure  12  using 

blocking between the floor joist.

 

  For floors supported by I-Joists, the method of anchorage 

is  illustrated  in  Figures  10  and  11.  Figure  12  illustrates  the 

general arrangement of anchorage to floor framing.

  It is important to take into consideration that the load for the 

Grand  Meridian  Fireplace  must  be  considered  as  additional 

dead load that will have to be supported by the floor framing. 

Additional floor joists or I-joists may be required as determined 

by the licensed design professional.

  The weights to be considered are noted in 

Table I

. It is the 

task and responsibility of the general contractor/installer to see 

that the proper reinforcement for weight loads are made by a 

licensed design professional prior to the fireplace installation.

  As stated above, it is desirable to place additional framing 

for alignment of anchor rods. Refer to 

Figure 14

 for anchor 

rod locations.

  Attach the firebox side wall anchors to steel support frame 

by inserting all-thread rods through holes on the bottom flange 

on the steel support frame as shown in 

Figure 14

. Secure with 

two Ø 2” o.d. x Ø 9/16” i.d. x 0.10” Washers and two 1/2-13 

UNC Nuts.

Figure 10

Floor Sheathing 

not shown for 

clarity

Metal Base 

Assembly

EXAMPLE ONLY

2X FLOOR JOIST

2X FLOOR JOIST

A35 Brackets 

(16 required)

I-JOISTS

Anchor 

Brackets

Figure 12

I-Joist 

Anchoring 

Bottom 

View

Example Only

I-Jo

ist

Simpson 

Strong-Tie 

A-35 or 

equivalent

Figure 11

I-Joist Anchoring 

Top View

Example Only

Summary of Contents for MMST43

Page 1: ...ns information that will enable you to obtain replacement parts or accessory items when needed Keep it with your other important papers WARNING THIS FIREPLACE IS APPROVED FOR USE AS A WOOD BURNING FIR...

Page 2: ...This page has been left intentionally blank...

Page 3: ...EEN TESTED FOR USE ONLY WITH APPROVED GLASS DOORS TO REDUCE THE RISK OF FIRE OR INJURY CONSULT OWNER S MANUAL THIS FIREPLACE IS DESIGNED FOR USE ONLY WITH SOLID WOOD LOGS PLUMBED LPG OR NG LOG LIGHTER...

Page 4: ...2 MMST43 Fireplace Parts Diagrams Combustible Floor Systems Non Combustible Floor Systems 1 3A 3 6 7 8 10 9 14 13 17 16 18 19 12 Figure 1 20 Figure 2 1 3A 3 6 7 8 10 9 14 13 19 12 20...

Page 5: ...43STFRBL Running Bond ITEM P N DESCRIPTION QTY 1 MFPST 43 1 HEARTH Left or Right 2 3 MFPST 43 3 SIDE WALL 5 3A MFPST 43 3A SIDE WALL W 4 KNOCKOUT 1 6 MFPST 43 6 LINTEL 1 7 MFPST 43 7 DOME SIDE LOWER 2...

Page 6: ...ure 3 Overall Dimensions Non Combustible Floor Systems Figure 4 IF WOOD FRAMING IS UTILIZED IT MUST BE HELD 18 INCHES MIN FROM TOP OF LINTEL AND 2 INCHES MIN CLEARANCE MUST BE MAINTAINED ALL AROUND FI...

Page 7: ...OF OPENING 20 1 2 THICK CONCRETE BOARD 8 METAL PLATFORM 2 INCH CLEARANCE TO COMBUSTIBLES BOTH SIDES OF FIREPLACE If using a raised hearth or metal base plate note that a combustible wood header must b...

Page 8: ...ance manufacturer s literature regarding sizing and suitability for the installation into this Enclosure prior to installation Statement of Intended Use The Grand Meridian Fireplace is a modular refra...

Page 9: ...s Spacing and clearance as it relates to combustible materials Familiarity of installation for all components The strength of the floor on which it rests Chimney system measurements Choice of material...

Page 10: ...responsibility of the contractor installer not the manufacturer to ensure that adequate combustion air is provided for proper function of this fireplace Fireplaces take up a large volume of replacemen...

Page 11: ...ts Note that additional floor joists may be required to support the weight of the firebox and chimney Where the floor joists run parallel to the front of the firebox anchorage can be accomplished in l...

Page 12: ...rs having a moisture content of less than 16 per cent at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted for the deflection resul...

Page 13: ...ng an on site constructed hearth extension you may use a sand cement grout between the hearth and extension instead What You Will Need You will find that the Grand Meridian Fireplace is designed to be...

Page 14: ...Once you have inserted any shims you will want to cover any gaps that may have resulted with the mortar MMST43 Fireplace Assembly 1 Place the Grand Meridian Fireplace hearth base on top of your non c...

Page 15: ...7 Set the remaining lintel as shown in Figure 22 8 Now you are ready to start the smoke dome assembly Take the lower side dome positioned so that the beveled face lines up with the inward angles of th...

Page 16: ...hat where the Support Box is located Firestop Radiation Shields also provide complete separation from one floor space to another or attic space as required by most codes When the double wall pipe pass...

Page 17: ...dian Fireplaces they cannot take any liability or responsibility for they way the firebrick or the firebrick mortar performs It is not unusual in the course of the life of the firebrick or the firebri...

Page 18: ...p air to function properly and some local building codes may require outside combustion air to be provided If no make up air is provided improper flue drafting may occur creating negative pressure whe...

Page 19: ...the base of the Anchor Plate Apply ceramic blanket gasket to the gasket cement 2 Apply balance of gasket cement in a 1 4 one quarter inch bead on top of smoke dome top approx 3 3 inches outside of out...

Page 20: ...s of firewood at any given time Consider that this typical fuel load is three to four dry hardwood logs that are about 6 six inches to 8 eight inches in diameter 4 Without a grate for your firewood to...

Page 21: ...er seals that surround it If you find any cracks or openings around screws or nails seal them to avoid any roof or chimney chase leaks SURFACE CRACKS The Grand Meridian FIREPLACES are manufactured usi...

Page 22: ...ncrete slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MI...

Page 23: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Page 24: ...pect for any injury or damage to the building or structure in which the fireplace has been installed or to the persons or property therein arising out of the use misuse or installation of properly man...

Reviews: