Astria Fireplaces Marin 40STTMN Assembly, Installation And Operation Instructions Download Page 39

39

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Operation

900301-01 04/2017

Innovative Hearth Products
Marin™ See-Through B-Vent Gas Fireplaces

BURNER ADJUSTMENTS 

(QUALIFIED TECHNICIANS ONLY)

Flame Appearance and Sooting

Proper fl ame appearance is a fl ame which is 
blue at the base and becomes yellowish-orange 
in the body of the fl ame.  

When the appliance is fi rst lit, the entire fl ame 
may be blue and will gradually turn yellowish-
orange during the fi rst 15 minutes of operation. 
If the fl ame remains blue, or if the fl ame is 
orange with evidence of sooting (black tip), the 
air shutter opening may need to be adjusted.

If the air shutter opening is closed too far, 
sooting may develop. Sooting is indicated by 
black puffs developing at the tips of very long 
orange fl ames.  Sooting results in black deposits 
forming on the logs, appliance inside surfaces 
and on exterior surfaces adjacent to the vent 
termination.  

Sooting is caused by incomplete combustion 
in the fl ames and lack of combustion air enter-
ing the air shutter opening. To achieve a warm 
yellowish-orange fl ame with an orange body 
that does not soot, the shutter opening must be 
adjusted between these two extremes. 

Air Shutter Adjustment Guidelines

:

Amount of 

Primary Air

Flame 

Color

Air Shutter 

Adjustment

If air shutter is 
closed too far

Flame will 
be orange

Air shutter 
gap should be 
increased

If air shutter is 
open too far

Flame will 
be blue

Air shutter 
gap should be 
decreased

Figure 43 - Burner Flame Appearance 

Air Shutter Adjustment Guidelines

•  If there is smoke or soot present, fi rst check 

the log set positioning to ensure that the 
fl ames are not impinging on any of the logs.  
If the log set is properly positioned and a 
sooting condition still exists, then the air 
shutter opening should be increased.

•  The more offsets in the vent system, the 

larger the air shutter opening will need to 
be.

•  An appliance operated with the air shutter 

opened too far, may have fl ames that appear 
blue and transparent.  These weak, blue and 
transparent fl ames are termed anemic. 

•  Propane models may exhibit fl ames which 

candle or appear stringy. If this is present 
and persists, adjust the air shutter to a more 
closed position, then operate the appliance 
for a few more minutes to ensure that the 
fl ame normalizes and the fl ames do not 
appear sooty. 

The following chart is provided to aid you in 
achieving the correct air shutter adjustment 
for your installation.

Glowing Embers (Rockwool)

Summary of Contents for Marin 40STTMN

Page 1: ...appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareil Netouchez aucaninterrupteur Nepasvousservir des t l phones se trouvant dans le b timent...

Page 2: ...ITRE EL VIDRIO CALIENTE CAUSAR QUEMADURAS USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE LOS NI OS DEBEN NUNCA TOCAR EL VIDRIO L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas...

Page 3: ...uncionamiento Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio Mantenga la ropa mobiliario gasolina y otros l quido...

Page 4: ...e barrier becomes dam aged the barrier shall be re placedwiththemanufacturer s barrier for this appliance For use with barrier s Part No s J7420 INTRODUCTION The Millivolt appliances have a millivolt...

Page 5: ...TheInstallationmustconformtolocalcodesor in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition InCanada thecurrentCAN CGA B149 1 installation code The appli...

Page 6: ...ude THE CONVERSION SHALL BE CAR RIED OUT BY A MANUFACTURER S AUTHO RIZED REPRESENTATIVE IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANU FACTURER PROVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTI...

Page 7: ...so important Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies Figure 2 En raison des temp ratures lev es l appareildevrait treinstall dansu...

Page 8: ...y from the roof surface National Fuel Gas Code ANSI Z223 1 NFPA 54 CAN CGA B149 1 Multiple Terminations These appliances may vent adjacent to and at the same level with any other gas appliances includ...

Page 9: ...ee Figure 5 Mantels constructed of non combustible materials may be installed at any height above the appliance opening however donotallowanythingtohangbelowthefireplacehood Minimumclearancerequiremen...

Page 10: ...or detailed procedures Step 1 Page 11 Construct the appliance framing Position the appliance within the framing and secure with nailing brackets and floor anchor tabs Step 2 Page 13 Route gas supply l...

Page 11: ...nailing flanges Install the 8 nailing flanges as shown in Figure 8 using the existing screws Position the fireplace within the framing When required theflangesmaybebent90degreesby hand or with the ass...

Page 12: ...19 41 1 8 1045 37 3 4 959 40 1 4 1022 41 1041 37 940 34 1 8 867 23 1 2 597 27 3 4 705 23 7 8 607 41 1041 2 51 FRAMING SPACERS Top and both sides FINISHED WALL BRACKET Front and back edge of unit top S...

Page 13: ...mpounds are used in propane applications Be very careful that the pipe compound does not get inside the pipe It is recommended to install a sediment trap in the supply line as close as possible to the...

Page 14: ...both models A Millivolt Wiring See Figure 14 Install Optional Control Switch OFF ON wall switch or remote control receiver Install snap bushing onbrownwallswitchwire intocontrol switch knock out in s...

Page 15: ...o the left away from the fireplace The lower control compartment door on the side opposite the valve lifts on and off The millivolt control valve has a 3 8 10mm NPT thread inlet port Secure all joints...

Page 16: ...loor Joists and under the home to a ventilated crawlspace not considered part of the living area of the home NOTE Do not terminate outside air kit in attic space under any circumstances CAUTION NEVER...

Page 17: ...any ports are blocked or partially blocked clean out the ports With gas line installed run initial system checkout before closing up the front of the unit Follow the pilot lighting instructions provi...

Page 18: ...volcanic stone evenly over firebox floor 6 Install Vermiculite Place some vermiculite on the firebox floor around thegrate theentirebagofvermiculitewillNOTbeused DONOTPLACE ANY VERMICULITE ON THE BUR...

Page 19: ...nst The Grate Here Position Log 2 Over The Grate Bar And Slide It Against The Back Of The Grate Here Position Groove At The Bottom Of Log 2 Over The Grate Here And Slide It Against The Back Of The Gra...

Page 20: ...The Grate Rest Log 5 Against The Grate Here Log 5 Sits In Front Of The Grate STEP 5 NOTICE Marin40ST model fireplac es include barriers to reduce the risk of burns from hot viewing glass The barriers...

Page 21: ...ring that the gasket seats evenly as the door frame draws shut Fasten the latch located underneath the firebox floor to the door s vee flange Close the latch securely NOTE Front Face Assembly with bar...

Page 22: ...lation and Page 9 for Clearances Figure 27 Finishing Requirements This Area Must Remain Clear of Combustible Materials Top of Appliance 1 Min 25 mm Combustible Wall Framing Spacer Top of Door Frame Ho...

Page 23: ...y of the burner on off wall switch it may be due to the operation of this safety limit switch First allow the appli ance to cool then reset the safety switch by pushing the red reset button on the bac...

Page 24: ...une t l commande est utilis e pour contr ler le foyer nettoyez la soigneusement pour liminer la poussi re et les traces de graisse ou d huile Collez l tiquette sur le bo tier de la t l commande Figure...

Page 25: ...r s left side to the right until it disengages from the left corner post hole Pull the door diagonally to the left away from the fireplace Remove the modesty panel by pulling the bottomrightcornerofth...

Page 26: ...ter to the manifold side pressure test fitting and verify manifold pressure reads 3 5 water column 0 87 kPa for natural gas and 10 0 water column 2 49 kPa for propane gas Step 6 Refer to Figure 31 and...

Page 27: ...2 todisengage and swing the panel open from top On millivolt systems the piezo igniter Hi Lo flame adjustment knob and pilot and main gas ON OFF control knob are located on the modesty panel The gas...

Page 28: ...nfants ou les adultes peuvent subir des br lures s ils viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour em...

Page 29: ...tiquette sur la surface de la plaque de l interrupteur mural quicontr lelefoyer FigureA Choisissezlalangue qui est principalement parl e dans la r sidence du propri taire 2 Si une t l commande est ut...

Page 30: ...gas indicated on rating plate This appliance is not convertible for use with other gases unless a certified kit is used These appliances are designed to oper ate on natural gas or propane gas only The...

Page 31: ...ng thefirsttwoweeksofusetopreventthefilmfrom baking on making it very difficult to remove See Cleaning Glass on Page 34 Orifice Sizes Sea Level to High Altitude All Models These appliances are tested...

Page 32: ...ressure Port Main Gas Control Knob IN OUT SIT Millivolt Gas Valve Outside Combustion Air Controls Manyappliancesareequipped wheninstalled with an outside make up air vent system that is designed to pr...

Page 33: ...ly of the burner on off wall switch it may be due to the operationofthissafetylimitswitch Firstallow the appliance to cool then reset the safety switch by pushing the red reset button on it A To acces...

Page 34: ...before initial use and at least annually by a qualified service technician inspectionshouldincludeensuringthatventing system is unobstructed and vent components are properly assembled and not damaged...

Page 35: ...closure Panel see Figure 38 Retrieve the glass door Visually inspect the gasket on the backside of the frame Gasket surface must be clean free of irregularities and seated firmly Position the door in...

Page 36: ...evenly over firebox floor 6 Install Vermiculite Place some vermiculite on the firebox floor around the grate the entire bag of vermiculite will NOT be used DO NOT PLACE ANY VERMICULITE ON THE BURNER N...

Page 37: ...The Grate Here Position Log 2 Over The Grate Bar And Slide It Against The Back Of The Grate Here Position Groove At The Bottom Of Log 2 Over The Grate Here And Slide It Against The Back Of The Grate P...

Page 38: ...2 3 Grate Assembly 5 Position Small End Of Log 6 On The Notch Of Log 3 Here 6 4 Position The Round End Of Log 6 Against The Notch Of Log 4 Here Two Charred Spots Face The Front Position The Groove In...

Page 39: ...shutter opening must be adjusted between these two extremes Air Shutter Adjustment Guidelines Amount of Primary Air Flame Color Air Shutter Adjustment If air shutter is closed too far Flame will be o...

Page 40: ...ng conditions are present adjust accordingly If flame appears weak or sooty adjust the air shutter incrementally to a more open position until the proper flame appearance is achieved If flame remains...

Page 41: ...___________________ Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the appliance 2 The serial number...

Page 42: ...Volcanic Stone Bag of Vermiculite Replacement ember materials volcanic stone or vermiculite are available for use with these appli ances Order kits as part of the periodic maintenance of the applianc...

Page 43: ...Remote Two Button Timer On Off Or Timer Mode Cat No Model No Description H8860 RC S 1 Remote Control Cost Effective Solution Simple On Off operation Kit includes Remote and Receiver Manual or up to 3...

Page 44: ...d by long lateral runs too many elbows and or exterior portions of the systembeingexposedtocoldweather Alsoinspectwallstraps or plumbers s tape to ensure it is secure and in place Appliance Checkout Q...

Page 45: ...AND IMMEDIATELY CALL your service technician or gas supplier LIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE s F THE PILOT WILL NOT STAY LIT AFTER SEVERAL TRIES TURN THE GAS CONTROL knob to OFF and...

Page 46: ...LA VEILLEUSE NE RESTE PAS ALLUM E APR S PLUSIEURS TENTATIVES r glez la manette d admission du gaz la position OFF et appelez un technicien qualifi ou le fournisseur de gaz 10 Tournez le bouton de r g...

Page 47: ...ot flame it must impinge on thermocouple see Figure 45 on Page 40 Clean and or adjust pilot for maximum flame impingement on thermocouple Ensure that the connection between the valve and thermocouple...

Page 48: ...ty 1 Hood Black 40 J7536 2 2 Glass Enclosure Assembly 40 H6365 2 3 Log Set 55M04 1 4 Bag of Vermiculite H6319 1 5 Bag of Embers rockwool 88L53 1 6 Bag of Decorative Volcanic Stone 80L42 1 7 Burner Ass...

Page 49: ...2017 Innovative Hearth Products Marin See Through B Vent Gas Fireplaces NOTE See the tables on Page 48 for replacement parts applicables REPLACEMENT PARTS Cat No Model F0869 Marin 40STMN 3 2 14 5 6 4...

Page 50: ...______ _____________________________________________________ _____________________________________________________ _____________________________________________________ _______________________________...

Page 51: ...t re ood or acts of God b damages caused by abuse negligence misuse or unauthorized alteration or repair of the Product affecting its stability or performance The Product must be subjected to normal u...

Page 52: ...rices and also to discon tinue colors styles and products Consult your local distributor for fireplace code information Printed in U S A 2015 Innovative Hearth Products P N 900301 01 Rev D 04 2017 150...

Reviews: