-146-
Function
code
Name
Description
Default Modify
When the set frequency is higher than the
upper limit of the running frequency, the upper
limit of the running frequency is used for
running.
Setting range: P00.05–P00.03 (Max. output
frequency)
P00.05
Lower limit of
running frequency
The lower limit of the running frequency is the
lower limit of the output frequency of the VFD,
When the set frequency is lower than the
lower limit of the running frequency, the lower
limit of the running frequency is used for
running.
Note:
Max. output frequency ≥ Upper limit of
frequency ≥ Lower limit of frequency
Setting range: 0.00Hz–P00.04 (Upper limit of
running frequency)
0.00Hz
◎
P00.06
Setting channel of A
frequency
command
0: Keypad
1: AI1
2: AI2
3: AI3
4: High-speed pulse HDIA
5: Simple PLC program
6: Multi-step speed running
7: PID control
8: Modbus/Modbus TCP communication
9:
Profibus/CANopen/DeviceNet
communication
10: Ethernet communication
11: High-speed pulse HDIB
12: Pulse train AB
13:
EtherCat/Profinet/EthernetIP
communication
14: Programmable expansion card
15: Reserved
0
○
P00.07
Setting channel of B
frequency
command
15
○
P00.08
Reference object of
B frequency
command
0: Max. output frequency
1: A frequency command
0
○
P00.09 Combination mode 0: A
0
○