49
ASSA ABLOY Hospitality
66 8003 015-3
Appendix A: Quick reference of technical data
Note:
If external motion sensor is applicable, see
Installation manual Orion High Voltage
Thermostat
for technical data and information about installation.
Dimensions (WxHxD)
112 x 117 x 35 mm (4 13/32" x 4 19/32" x 1 3/8")
Mains voltage input
Universal voltage input 100VAC-277VAC; 50/60Hz;
rated impulse voltage: 4kV
Switch input
Door switch - 1 exterior/1 interior
Multifunction input
Motion sensor/card switch/pipe temp sensor
High voltage outputs
-
G1
(Fan 1): Type 1.B action. Max load 3A (3FLA/18LRA)
-
G2
(Fan 2): Type 1.B action. Max load 3A (3FLA/18LRA)
-
G3
(Fan 3): Type 1.B action. Max load 3A (3FLA/18LRA)
-
RV
(reversing valve): Type 1 action. Max load 0.5A
-
Y (
cooling/compressor): Type 1 action. Max load 0.5A
-
W
(heating): Type 1 action. Max load 0.5A
Low voltage outputs
-
Proportional 0-10V; heating
-
Proportional 0-10V; cooling
-
Switch output
(max 24V AC/DC, SELV, max 0.1A)
Temperature sensor
Integrated in thermostat
Temperature display
Configurable:
room temperature
(default)
or
guest setting
Temperature display range
2-digit display
Adjustable setpoint
temperature range
17°C - 32°C / 62F - 90F
Environment
Normal indoor environment - Pollution degree 2
Operating temperature range 0°C - 55°C / 32F -130F
Temperature sensor
Integrated in thermostat
Service device
Orion Service
software and
service cable RJ12 to 3.5mm stereo jack
Radio (RF) signals
ZigBee 2006
Lock to thermostat:
Door open - staff card
Door open - guest card
Door open from inside
Door closed
Deadbolt thrown/released
Thermostat to lock:
Room occupied
Motion sensor to thermostat:
Motion detected
Battery status
Thermostat to motion sensor:
Turn off when the room is occupied and door is closed
Turn on when the door is opened again