33
EN
Safety instructions
Important!
Unprotected wiring can be manipulated:
The electronic door components are
interconnected and controlled via the wiring. The wiring must be installed in a
manner such that it is protected from manipulation and disturbances, and may
not be accessible from outside.
Property damage from connection with USB devices:
The connection socket on
the housing cover (Fig. 2 page 30 –
1
) is
not a USB jack
. The device will be
destroyed if a USB device is connected via a standard USB cable A/B.
· Only use the
ePED Service Interface USB 1386–SIF
.
Note!
The bus system must be terminated:
The bus system must be terminated with
a terminating resistor arranged as close to the centre as possible. The longest
branch connection line may not be longer than 10 m.
Use of motorised locks in systems with fire doors (smoke control doors):
The
OneSystem
®
IO module N5951
must, when
used in systems with fire doors (smoke
control doors),
be combined with
fire protection module 519ZBFS
. All applicable
provisions for the approval of protective doors must be observed here.
A
I
Summary of Contents for N5951000PILL000
Page 25: ...25 DE ...
Page 49: ...49 EN ...
Page 73: ...73 FR Accessoires entretien garantie élimination ...
Page 97: ...97 IT ...
Page 121: ...121 NL Toebehoren onderhoud garantie afvalverwijdering ...
Page 122: ...122 NL ...
Page 123: ...123 NL ...