Configuration
Test function of the door
The test may have to be carried out by two people at the door and the controlling
CMC box.
Warning!
Risk of death if a test result is incorrectly interpreted:
If, during a test, a con-
crete door is sent a release request from a further door at the same time, this
second signal can be erroneously interpreted as a successful test result. An instal-
lation not carried out properly therefore remains undiscovered and the door is
not released in case of danger.
· Ensure that only the door to be tested can be operated.
1 Person 1: Trigger a local Emergency Open.
Person 2: The controlling CMC box displays a release request.
2 Person 2: Extend the delay time via the controlling CMC box.
3 Person 1: Check whether an extended waiting time
is displayed on the door terminal.
The test is successful if the extended release delay is displayed on the door
terminal. There is a connection between the door and escape door control
unit.
Check CMC connector
Green LED
Yellow LED Red LED
Description
Flashes
Off
(As required)
CMC connector
is connected to all
assigned
CMC boxes
Flashes
On
(As required) At least one
CMC box
is not connected
or sends an incorrect ID or the
assignment is incorrect
Off
On
(As required) "Local mode": no connection to
CMC boxes
(As required) (As required) On
Door is locked
(As required) (As required) Off
Door is released
!
Tab. 5:
Check CMC
connector