Safety instructions
Intended use
Electrical locking devices on doors along escape routes are intended for use in
commercial applications.
The
ePED
®
1386CMC central escape route control system
is a central operating panel
with which authorised persons monitor and operate the electrically-controlled
escape door system.
The escape door system is equipped with
ePED
®
escape route technology
. The
Ethernet connection is established with an
ePED
®
CMC Connector 1386CMC-CON
on every escape door (manual
D01118xx ePED
®
CMC Connector 1386CMC-CON
),
with the following applicable limits:
· a
1386CMC central escape route control
can control a maximum of 126 escape
doors via
126 CMC connectors 1386CMC-CON
,
and
· one escape door can be controlled by no more than 32 1386CMC central es-
cape route control systems via a 1386CMC-CON CMC connector.
The product has been designed for safeguarding escape routes and has been
tested to the requirements specified in the German guidelines on electrical
locking systems for doors in escape routes (EltVTR). Deviating uses or device
combinations not described are not permitted.
Security personnel must be able to see the affected escape door directly or via
video monitoring. It is not permissible to extend the release time or blocking
without being able to see the escape door.
ASSA ABLOY Sicherheitstechnik GmbH
can provide the necessary planning information
for approved solutions and the device combinations required for your application.
The security functions for the release of the electrical locking meet the require-
ment for fail-safe functionality in DIN EN 13637:2015, “safety integrity level” SIL 2
of the IEC 61508:2010 parts 1 to 7 (reference: technical data).
Compliance with all relevant inspection authority requirements is mandatory for
use, particularly with respect to the
· coordination of the safety concept with the responsible inspection authority
and
· modifications of door elements.
The relevant inspection authority must approve before activation/use of release
blocking and/or release delay.
The device is suitable for installation, configuration and use, according to these
instructions. Any use beyond this is deemed as non-intended use; devices
combinations which are not described are not permitted.