OM00020 Rev 2, FP00091, FP00101 Operation Manual 

Page 

12

 of 

15

 

 

Table 4: RMC RS-485 Communication Pinout 

Pin 2 

 RX/D- 

Pin 3 

 TX/D+ 

Pin 5 - GND 

 

The default communications settings are as follows, but they can be adjusted if required. 

 

Serial address: 1 

 

Serial baudrate: 19200 

The relevant parameters for the RMC and their Application Data Unit (ADU) are defined in the Table 1 
below: 

Table 5: Modbus parameters 

LABEL 

DESCRIPTION 

MIN 

MAX 

VALUE/TYPE 

UNIT 

RW 

ADU 

  

PARAMETERS & STATUS VARIABLES 

  

  

  

  

  

  

StU 

General > Setup 

  

  

  

  

  

  

y01 

ON/OFF 

0 - OFF 

Enum 1 

RW 

3001 

y05 

Temperature Units 

0 - C 

Enum 6 

RW 

3002 

y07 

Restore default parameters 

0 - NO 

Enum 2 

RW 

3003 

y08 

Control Sensor 

0 - TI 

Enum 7 

RW 

3030 

y09 

Control Mode 

0 - Def 

Enum 8 

RW 

3031 

ALA 

General > Configuration 

  

  

  

  

  

  

BUZ 

Buzzer activation time 

15 

min 

RW 

3004 

AdL 

Alarm relay activation delay 

999 

RW 

3005 

AOF 

Alarm relay active if unit in OFF 

1 - YES 

Enum 2 

RW 

3006 

SEr 

General > Serial settings 

  

  

  

  

  

  

SEr 

Serial address (Modbus and CAN) 

100 

  

RW 

3007 

bAU 

Serial baudrate (Modbus) 

6 - 192 

Enum 3 

RW 

3008 

COM 

Serial settings (Modbus) 

0 - 8N1 

Enum 4 

RW 

3009 

CFG 

Parameters > Unit config 

  

  

  

  

  

  

SEt 

Setpoint 

-20 

90 

21.0 

°C 

RW 

3013 

c01 

Pump Flow Delay 

100 

10 

RW 

3014 

c02 

Fan Delay Off 

100 

RW 

3015 

c03 

T1-Pv Filter 

100 

  

RW 

3016 

c04 

Alarm Diff 

100 

5.0 

RW 

3017 

c05 

Pump Shutdown Delay 

100 

RW 

3018 

c06 

Min Compr Speed 

100 

20 

RW 

3019 

c07 

Pump Speed 

80.0 

RW 

3020 

c08 

Compr Delay Off 

3600 

60 

RW 

3021 

c09 

Max Pump Speed 

100 

100.0 

  

RW 

3028 

c10 

Min Pump Speed 

0.0 

  

RW 

3029 

PID 

Parameters > PID Settings 

  

  

  

  

  

  

P01 

Regulation Type 

2 - PID 

Enum 5 

RW 

3022 

P02 

Gain 

1000 

2.0 

  

RW 

3023 

Summary of Contents for FP00091

Page 1: ...Dr Marlborough MA 01752 Installation and Operation Instructions Rack Mount Chiller RMC 800 RMC 1100 FP00091 FP00101 Installations Notes Date of Purchase Date of Installation Installer Model Number Se...

Page 2: ...nal Thermistor 6 Performance 6 Cooling Capacity 6 Performance Curves 6 Coolant Flow Rate 7 Controller Interface 8 Primary Functionality 8 Changing the Setpoint 8 Starting the RMC 9 Turning off the RMC...

Page 3: ...g substance ODS alternative In the event that the RMC is damaged general work clothing leather gloves and eye protection should be worn to prevent exposure to refrigerants The RMC also contains Polyol...

Page 4: ...e coolant loop The presence of foreign materials into the RMC could damage components and reduce system performance Aspen recommends that the customer use an external filter prior to the return line t...

Page 5: ...e reservoir If operating in an environment where the coolant temperature is below the dew point of the ambient air these surfaces will collect condensation To prevent condensation from forming these s...

Page 6: ...e harness that consists of a mating connector and a NTC 10 kOhm thermistor Type 2 The type of thermistor is dependent on the customer s application but Aspen can provide guidance if needed Performance...

Page 7: ...erformance Map Figure 6 RMC 800 Performance Map Coolant Flow Rate The RMC is equipped with a positive displacement pump Using Koolance 702 as a coolant the system can generate the following maximum fl...

Page 8: ...ed with a controller which monitors and controls the system The primary interface of the system is shown in Figure 8 below Figure 8 Controller Interface During normal operation the controller displays...

Page 9: ...rature at the supply CPC default 2 The RMC controls to an external input thermistor see External Thermistor p 6 3 The RMC controls to an internal temperature which is 1 C greater than an external ambi...

Page 10: ...p y01 ON OFF y05 Temperature units y07 Restore default parameters y08 Control sensor y09 Control mode ALA Configuration BUZ Buzzer activation time AdL Alarm relay activation delay AOF Alarm relay acti...

Page 11: ...a fault occurs the user must clear the fault to resume operation of the system To clear a fault the user must do the following Press Press 2 times to reach the Str screen Press Press 2 times to reach...

Page 12: ...3031 ALA General Configuration BUZ Buzzer activation time 0 15 1 min RW 3004 AdL Alarm relay activation delay 0 999 0 s RW 3005 AOF Alarm relay active if unit in OFF 0 1 1 YES Enum 2 RW 3006 SEr Gener...

Page 13: ...18 POWER UP 32768 32767 0 Read 8119 V19 Cur Setpoint 32768 32767 0 Read 8120 HLD Main Menu Hold P04 Derivative Time 0 10000 90 s RW 3025 P05 Overshooting 0 500 150 RW 3026 P06 Filter Factor Derivative...

Page 14: ...notice promptly given will either examine the product at buyer s site or issue shipping instructions for return to Aspen at buyer s expense transportation charges prepaid Aspen s sole obligation unde...

Page 15: ...eplaced at the discretion of Aspen Systems LLC Depending on the circumstances of the problem it may be deemed necessary to return the products to Aspen Systems for repair In order to return the produc...

Reviews: