Output signals
POSIHALL
®
Analog output, programmable
)
Signal wiring
Signal
Connector
pin no.
Cable color
Exci
1
brown
Signal
2
white
GND
3
blue
Do not connect!
4
black
SPAN/ZERO
5
grey
View to sensor
connector
Option -PMU
Programming of the start and end value by the customer
Teach-In of start and end value for the options U2/PMU, I1/PMU, U8/PMU is provided by a binary si-
gnal SPAN/ZERO. At the start position connect signal SPAN/ZERO for a period of 2 … 3 seconds to
GND via push button. At the end position connect signal SPAN/ZERO for a period of 5 … 6 seconds
to GND via a push button. The teached positions will be stored non-volatile.
To reset the sensor to factory default signal ZERO/END must be connected to ground while powering
up the sensor for 2 … 3 seconds.
A-Codification
Option -PMZ
Programming of the start value by the customer
Programming of the start value of the output range for the outputs U2/U8 and I1 is provided by a pro-
gramming signal ZERO available at the connector. This Signal ZERO must be connected with GND
via a push button, and then the position magnet of the sensor must be moved to the start resp. the
end position. Pushing the button between 1 and 4 seconds sets the actual position as start position,
pushing the button more than 5 seconds sets the actual position as end position. The values will be
stored and are available after switching off the sensor.
To reset the sensor to the factory values the button must be pushed when the sensor is switched on.