Figure 7: Rear Serial port terminal block
For connecting the RS422/ RS485, use screened cable with a maximum total length of 1000
m or 200 nF total cable capacitance.
A typical cable specification would be:
Each core: 16/0.2 mm
2
copper conductors, PVC insulated
Nominal conductor area: 0.5 mm
2
per core
Screen: Overall braid, PVC sheathed
There is no electrical connection of the cable screen to the device. The link is provided
purely to link together the two cable screens.
2.3.8
Power Supply Connections
These should be wired with 1.5 mm PVC insulated multi-stranded copper wire terminated
with M4 ring terminals. The wire should have a minimum voltage rating of 300 V RMS.
As per the application, in case auxiliary supply input of the relay needs to be wired, then
adequate care should be taken to wire as per polarity marking on the Terminal sticker at the
rear of the relay. The supply range is also mentioned on the Terminal sticker and before
energising, care should be taken to confirm that the auxiliary supply being wired is within
range.
2.3.9
Earth Connection
Every device must be connected to the earthing terminal. Earthing terminal is provided on
back side of the relay. Ensure that the relay earthing is connected to the local earth bar. With
several relays present; make sure that the copper earth bar is properly installed for solidity
connecting to the earthing terminal of each relay equipment box.
Before energizing the equipment it must be earthed using the protective conductor terminal,
(if provided) or the appropriate termination of the supply plug in the case of plug connected
equipment. The protective conductor (earth) connection must not be removed since the
protection against electric shock provided by the equipment would be lost. The
recommended minimum protective conductor (earth) wire size is 2.5 mm² or as per industries
standard practice. The protective conductor (earth) connection must be of low-inductance
and as short as possible.
Summary of Contents for ADR141A
Page 10: ...Page intentionally Left Blank...
Page 16: ...Page intentionally Left Blank...
Page 28: ...Page intentionally Left Blank...
Page 43: ...Page intentionally Left Blank...
Page 53: ...Page intentionally Left Blank...
Page 69: ...Page intentionally Left Blank...
Page 73: ...Page intentionally Left Blank...
Page 80: ...Page intentionally Left Blank...
Page 92: ...Page intentionally Left Blank...
Page 122: ...Page intentionally Left Blank...
Page 136: ...Page intentionally Left Blank...
Page 140: ...ADR141A ADR241A Doc ID ADR241A_IM_01 Ref ID ADR241A IM DR Rev No 02 Page No 140 of 150...
Page 141: ...Page intentionally Left Blank...
Page 151: ......